{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1016-1AV02","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1016-1AV02","canonicalUrl":"https://aoctrl.com/siemens/3RT1016-1AV02","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1016-1AV02","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, Size S00, 3RT1016-1AV02, 24 VDC coil, 10 A rated operating current at AC-12, screw terminals, 45 mm width.","salesMarkdown":"The 24 VDC coil draws its rating from a control transformer or DC supply; the contactor is rated for 10 A at AC-12 (resistive) and handles motor starting at 4 kW at 400 V AC-2 duty. For heavy inching or plugging duty (AC-4), the rated operational current is 8.5 A at 400 V. The DC coil control voltage is 24 VDC, with a rated value of 10 A at 24 V for the main contacts. The coil operates across a range of 0.8 to 1.1 times rated voltage at 50 Hz and 0.85 to 1.1 at 60 Hz. Snap-on mounting onto a 35 mm DIN rail per EN 50022 is standard; the 45 mm width and 57.5 mm height allow dense packing in a standard enclosure. Screw-type terminals on the main circuit accept 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or max 2x (0.75 to 4 mm²) solid or stranded conductors. AWG equivalents are 2x (20 to 16), 2x (18 to 14), or 1x 12. The enclosure offers IP20 protection on the front and at the terminals. Pollution degree 3 applies. ## Motor Ratings and Coordination For three-phase motor loads at 400 V, the contactor is rated 4 kW in AC-2 duty (starting only) and 5.5 kW at 690 V. At 500 V, the rating is 4.5 kW. The AC-3 rating (starting and running) is not separately stated in the evidence, but the AC-2 and AC-4 figures cover the typical motor switching envelope. Short-circuit coordination: with type 2 coordination, a gL/gG fuse of 20 A is required; with type 1 coordination, a 35 A fuse. The contactor has a mechanical life of 30 million operations typical.","metaTitle":"Siemens 3RT1016-1AV02 SIRIUS Power Contactor, Size S00, 24 V","metaDescription":"Siemens SIRIUS 3RT1016-1AV02 power contactor, Size S00, 24 VDC coil, 10 A rated current. Current lifecycle. Sourced to order against RFQ. Specifications: 45 mm width, 57.5 mm heigh","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"57.5 mm","Maximum":"2 000 m","at 50 Hz":"0.8 ... 1.1","at 60 Hz":"0.85 ... 1.1","At The Side":"6 mm","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"400 V","at 500 V rated value":"4.5 kW","at 60 Hz rated value":"400 V","at 690 V rated value":"5.5 kW","Instantaneous Contact":"0","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","at AC-2 at 400 V rated value":"4 kW","at AC-4 at 400 V rated value":"8.5 A","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"screw-type terminals","at ambient temperature 40 °C rated value":"22 A","Apparent holding power of magnet coil at AC":"4.4 V·A","Apparent pick-up power of magnet coil at AC":"27 V·A","Type of voltage of the control supply voltage":"AC","Inductive power factor with closing power of the coil":"0.8","Inductive power factor with the holding power of the coil":"0.27","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=410025&mlfb=3RT1016-1AV02","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1016-1AV02/alternatives.json"},"ai":{"faq":[{"question":"What is 3RT1016-1AV02's listed depth?","answer":"The depth is 72 mm, with a width of 45 mm and height of 57.5 mm."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1016-1AV02","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1016-1AV02 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}