{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1016-1BB41-ZW97","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1016-1BB41-ZW97","canonicalUrl":"https://aoctrl.com/siemens/3RT1016-1BB41-ZW97","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1016-1BB41-ZW97","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S00, order code 3RT1016-1BB41-ZW97, 24 VDC coil, screw-type terminals, 45 mm width, IP20 front protection.","salesMarkdown":"The AC-12 operating current is 10 A, which is the rating for resistive loads like heaters or lighting ballasts — that's the full continuous capability through the main contacts. For motor switching, the AC-3 rating (not directly listed here but implied by the 4 kW at 400 V AC-2 and 8.5 A AC-4) tells you this contactor handles small motors up to about 4 kW at 400 V under normal starting duty. The DC switching ratings matter if you're using it for DC loads: 10 A at 24 V, 2 A at 60 V, 1 A at 110 V, and 0.3 A at 220 V. These are the maximum break currents for DC circuits — DC arcs are harder to extinguish than AC, so these numbers are lower than the AC ratings. If you're switching a DC brake coil or a solenoid valve, stay within these curves. This is your selectivity planning number — coordinate downstream so the fuse clears before the contactor welds. The contactor is 45 mm wide, 57.5 mm tall, and 72 mm deep — that's a compact footprint for a size S00 device. Screw-type terminals on the main circuit accept 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or up to 2x (0.75 to 4 mm²) solid or stranded wire. AWG equivalents are 2x (20–16), 2x (18–14), and 1x 12. The front has IP20 finger protection, so the panel builder doesn't need additional terminal shrouds for touch safety. The closest functional peer is the 3RT1015-1BB42, which shares the same size S00 frame and 24 VDC coil but has a lower AC-12 current rating (typically 7 A vs 10 A) and different terminal style. If your load is under 7 A and you need spring-cage terminals, that's the alternate — but for 10 A resistive or the full motor rating, stick with this order code.","metaTitle":"Siemens 3RT1016-1BB41-ZW97 SIRIUS Power Contactor, Size S00,","metaDescription":"Siemens SIRIUS 3RT1016-1BB41-ZW97 power contactor, size S00, 24 VDC coil, 10 A at 24 V, AC-12 rated 10 A, screw terminals, IP20 front, DIN rail mount, active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"57.5 mm","Maximum":"2 000 m","At The Side":"6 mm","Rated Value":"24 V","On The Front":"IP20","Initial Value":"0.85","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Full-scale value":"1.1","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 500 V rated value":"4.5 kW","at 690 V rated value":"5.5 kW","Instantaneous Contact":"1","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","at AC-2 at 400 V rated value":"4 kW","at AC-4 at 400 V rated value":"8.5 A","Closing power of magnet coil at DC":"3.3 W","Holding power of magnet coil at DC":"3.3 W","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"screw-type terminals","at ambient temperature 40 °C rated value":"22 A","Type of voltage of the control supply voltage":"DC","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=198358&mlfb=3RT1016-1BB41-ZW97","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1016-1BB41-ZW97/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional alternative — the 3RT1015-1BB42?","answer":"The 3RT1015-1BB42 is a size S00 contactor with a 24 VDC coil but uses spring-cage terminals and has a lower AC-12 rating (7 A vs 10 A). It fits the same DIN rail footprint and can replace the 3RT1016-1BB41-ZW97 only if your load current is under 7 A and you prefer tool-less wiring."},{"question":"What are the main contact ratings for this contactor?","answer":"AC-12 resistive switching is rated 10 A. For motor duty, AC-2 at 400 V is 4 kW, and AC-4 at 400 V is 8.5 A. DC ratings are 10 A at 24 V, 2 A at 60 V, 1 A at 110 V, and 0.3 A at 220 V."},{"question":"What fuse protection is required for Type 2 coordination?","answer":"Type 2 coordination requires a gL/gG fuse rated 20 A. Type 1 coordination allows a 35 A fuse. This assumes the short-circuit current does not exceed the contactor's rated breaking capacity."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1016-1BB41-ZW97","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1016-1BB41-ZW97 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}