{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1016-1BB41-ZX95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1016-1BB41-ZX95","canonicalUrl":"https://aoctrl.com/siemens/3RT1016-1BB41-ZX95","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1016-1BB41-ZX95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, 3RT1016-1BB41-ZX95, size S00, 24 VDC coil, 4 kW at 400 V AC-3, screw terminals, IP20 front, DIN rail mount.","salesMarkdown":"The 45 mm width and 57.5 mm height fit the standard S00 footprint; depth is 72 mm, which matters when the panel depth is tight against a backplate or door. Side-by-side mounting is permitted, with 6 mm spacing at the side — no forced air gap, but the 20 A gL/gG fuse (type 2 coordination) or 35 A (type 1) sets the short-circuit protection upstream. Screw terminals accept 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or max 2x (0.75 to 4 mm²) solid or stranded — covers the common panel wire sizes without needing ferrules for the smaller gauges.","metaTitle":"Siemens 3RT1016-1BB41-ZX95 SIRIUS Power Contactor, 24 VDC Co","metaDescription":"Siemens 3RT1016-1BB41-ZX95 SIRIUS power contactor, size S00, 24 VDC coil, 4 kW at 400 V AC-3. IP20 front, screw terminals, DIN rail mount. Current lifecycle. Sourced to order again","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"57.5 mm","At The Side":"6 mm","Rated Value":"24 V","On The Front":"IP20","Initial Value":"0.85","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Full-Scale Value":"1.1","Size Of Contactor":"S00","Solid Or Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","Product Brand Name":"SIRIUS","Degree Of Pollution":"3","Product Designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 400 V rated value":"4 kW","at 500 V rated value":"4.5 kW","at 690 V rated value":"5.5 kW","Instantaneous Contact":"1","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","at AC-2 at 400 V rated value":"4 kW","at AC-4 at 400 V rated value":"8.5 A","at AWG cables for main contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","For Auxiliary And Control Circuit":"screw-type terminals","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","closing power of magnet coil at DC":"3.3 W","holding power of magnet coil at DC":"3.3 W","reference code acc. to IEC 81346-2":"Q","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","operational current at AC-12 maximum":"10 A","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","at ambient temperature 40 °C rated value":"22 A","Type Of Voltage Of The Control Supply Voltage":"DC","operational current at AC-15 at 230 V rated value":"6 A","operational current at AC-15 at 400 V rated value":"3 A","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","type of connectable conductor cross-sections at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=470125&mlfb=3RT1016-1BB41-ZX95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1016-1BB41-ZX95/alternatives.json"},"ai":{"faq":[{"question":"What is the coil voltage and power draw for 3RT1016-1BB41-ZX95?","answer":"The coil is rated 24 V DC, drawing 3.3 W for both closing and holding power."},{"question":"What motor power can this contactor switch at 400 V?","answer":"Rated 4 kW at 400 V AC-3 duty for standard motor starting, and 8.5 A at 400 V AC-4 for reversing or plugging applications."},{"question":"What are the mounting dimensions of 3RT1016-1BB41-ZX95?","answer":"Width 45 mm, height 57.5 mm, depth 72 mm. Mounts on 35 mm DIN rail per EN 50022 with snap-on fastening."},{"question":"What wire sizes does the screw terminal accept?","answer":"Accepts 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or max 2x (0.75 to 4 mm²) solid or stranded conductors."},{"question":"Where can I buy 3RT1016-1BB41-ZX95?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1016-1BB41-ZX95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1016-1BB41-ZX95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}