{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1016-1BB42-ZW97","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1016-1BB42-ZW97","canonicalUrl":"https://aoctrl.com/siemens/3RT1016-1BB42-ZW97","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1016-1BB42-ZW97","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S00, 3RT1016-1BB42-ZW97, 24 VDC coil, screw terminals, 10 A AC-12, 4 kW AC-2 at 400 V, IP20 front.","salesMarkdown":"The 24 VDC coil pulls in at 85% of rated voltage (20.4 V) and drops out at 110% (26.4 V), with a closing and holding power of 3.3 W — a constant DC draw that matters for power supply budgeting on a control transformer or DC bus. Rated for AC-12 duty at 10 A, this contactor handles resistive loads at up to 690 V. For motor switching, it delivers 4 kW in AC-2 at 400 V (part-winding start) and 8.5 A in AC-4 at 400 V (plugging/inching). The AC-3 motor rating hits 4.5 kW at 500 V and 5.5 kW at 690 V, covering common European 400 V and 690 V industrial supplies. ## Fit, mounting, and wiring The S00 frame is a 45 mm wide, 57.5 mm tall, 72 mm deep block — tight enough for high-density panels. Screw terminals on the main circuit accept solid or stranded copper: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or max 2x (0.75 to 4 mm²). AWG equivalents are 2x (20 to 16), 2x (18 to 14), or 1x 12. Strip length and torque follow standard Siemens practice for S00 screw terminals — no special tooling needed. Type 1 allows up to 35 A.","metaTitle":"Siemens 3RT1016-1BB42-ZW97 SIRIUS S00 Power Contactor, 24 VD","metaDescription":"Siemens SIRIUS 3RT1016-1BB42-ZW97 power contactor, size S00, 24 VDC coil, 10 A AC-12, 4 kW AC-2 at 400 V. Screw terminals, IP20. Current lifecycle stage. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"57.5 mm","Maximum":"2 000 m","At The Side":"6 mm","Rated Value":"24 V","On The Front":"IP20","Initial Value":"0.85","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Full-scale value":"1.1","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 500 V rated value":"4.5 kW","at 690 V rated value":"5.5 kW","Instantaneous Contact":"0","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","at AC-2 at 400 V rated value":"4 kW","at AC-4 at 400 V rated value":"8.5 A","Closing power of magnet coil at DC":"3.3 W","Holding power of magnet coil at DC":"3.3 W","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"screw-type terminals","at ambient temperature 40 °C rated value":"22 A","Type of voltage of the control supply voltage":"DC","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=435702&mlfb=3RT1016-1BB42-ZW97","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1016-1BB42-ZW97/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1016-1BB42-ZW97","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1016-1BB42-ZW97 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}