{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1016-1DB41-ZX95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1016-1DB41-ZX95","canonicalUrl":"https://aoctrl.com/siemens/3RT1016-1DB41-ZX95","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1016-1DB41-ZX95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S00, 24 V DC coil, screw terminals, 5.5 kW at 690 V, IP20 front, DIN rail mount.","salesMarkdown":"Siemens SIRIUS 3RT1016-1DB41-ZX95 is a size S00 power contactor with a 24 V DC coil, rated for motor loads up to 5.5 kW at 690 V. The front is IP20, so it's fine for enclosed panels but not washdown areas. The 24 V DC coil picks up at 85% of rated voltage (about 20.4 V) and holds at 110% (26.4 V), with a constant 3.3 W draw closing and holding — no AC inrush to worry about on your DC supply. Switching capacity: 10 A at AC-12 (resistive loads), 6 A at 230 V, 3 A at 400 V, and 4.5 kW at 500 V or 5.5 kW at 690 V for motor duty. For AC-4 (frequent reversing or inching) at 400 V it's rated 8.5 A. The auxiliary contact is a single instantaneous N/O. The varistor surge suppressor is built in across the coil — no external snubber needed for standard inductive loads. Size S00 footprint: 45 mm wide, 57.5 mm tall, 111 mm deep. Wire range: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or max 2x (0.75 to 4 mm²) solid/stranded — spring-cage not available, these are screw terminals. The altitude rating is 2,000 m max; above that, derate per IEC 60947.","metaTitle":"Siemens 3RT1016-1DB41-ZX95 SIRIUS Power Contactor, 24 VDC, 5","metaDescription":"Siemens SIRIUS 3RT1016-1DB41-ZX95 power contactor, 24 VDC coil, 5.5 kW at 690 V, size S00. Active production. Screw terminals, DIN rail mount. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"111 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"57.5 mm","Maximum":"2 000 m","At The Side":"6 mm","Rated Value":"24 V","On The Front":"IP20","Initial Value":"0.85","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Full-scale value":"1.1","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 500 V rated value":"4.5 kW","at 690 V rated value":"5.5 kW","Instantaneous Contact":"1","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","at AC-2 at 400 V rated value":"4 kW","at AC-4 at 400 V rated value":"8.5 A","Design of the surge suppressor":"with varistor","Closing power of magnet coil at DC":"3.3 W","Holding power of magnet coil at DC":"3.3 W","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"screw-type terminals","at ambient temperature 40 °C rated value":"22 A","Type of voltage of the control supply voltage":"DC","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=173128&mlfb=3RT1016-1DB41-ZX95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1016-1DB41-ZX95/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3RT1016-1DB41-ZX95?","answer":"Submit an RFQ against this listing; we confirm availability and current pricing at quote time through our distribution network."},{"question":"What is the depth of 3RT1016-1DB41-ZX95?","answer":"The depth is 111 mm."},{"question":"What wire sizes does the screw terminal accept?","answer":"Solid or stranded: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or max 2x (0.75 to 4 mm²). AWG equivalents: 2x (20 to 16), 2x (18 to 14), 1x 12."},{"question":"Will 3RT1016-1DB41-ZX95 drop into a panel specified around 3RT1016-1AG61 without rewiring?","answer":"Both are size S00 with the same footprint (45 mm wide, 57.5 mm tall, 111 mm deep) and screw terminals, so mechanical fit and wiring are identical. The difference is the coil voltage: 24 V DC on this one versus the peer's coil. Check your control supply before swapping."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1016-1DB41-ZX95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1016-1DB41-ZX95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}