{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1016-1JB41-ZW97","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1016-1JB41-ZW97","canonicalUrl":"https://aoctrl.com/siemens/3RT1016-1JB41-ZW97","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1016-1JB41-ZW97","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT1016-1JB41-ZW97 power contactor, size S00, 24 VDC coil with integrated diode suppression, screw terminals, snap-on DIN rail mounting.","salesMarkdown":"At 400 V AC-3 duty it switches 4 kW motor loads; at 690 V that rises to 5.5 kW, making it suitable for 400 V line-fed conveyor drives in a warehouse shuttle system. Short-circuit coordination is specified: Type 2 coordination requires a 20 A gL/gG fuse; Type 1 allows a 35 A fuse. This matters for panel selectivity—if you need the contactor to survive a fault without replacement, spec the 20 A fuse upstream. The screw terminals accept 2x (0.5 to 1.5 mm²) solid, 2x (0.75 to 2.5 mm²) stranded, or up to 1x 12 AWG. The 45 mm width and 72 mm depth fit standard 35 mm DIN rail per EN 50022, with 6 mm clearance needed at the side for heat dissipation. ## Integration notes Side-by-side mounting is permitted, but derate per the thermal curve above 40 °C ambient.","metaTitle":"Siemens 3RT1016-1JB41-ZW97 SIRIUS Power Contactor, S00, 24 V","metaDescription":"Siemens SIRIUS 3RT1016-1JB41-ZW97 power contactor, size S00, 24 VDC coil, 10 A rated current. Active production. Screw terminals, snap-on DIN rail. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"57.5 mm","Maximum":"2 000 m","At The Side":"6 mm","Rated Value":"24 V","On The Front":"IP20","Initial Value":"0.7","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Full-scale value":"1.25","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 500 V rated value":"4.5 kW","at 690 V rated value":"5.5 kW","Instantaneous Contact":"1","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","at AC-2 at 400 V rated value":"4 kW","at AC-4 at 400 V rated value":"8.5 A","Design of the surge suppressor":"with diode","Closing power of magnet coil at DC":"2.3 W","Holding power of magnet coil at DC":"2.3 W","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"screw-type terminals","at ambient temperature 40 °C rated value":"22 A","Type of voltage of the control supply voltage":"DC","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=411242&mlfb=3RT1016-1JB41-ZW97","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1016-1JB41-ZW97/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional alternative to the 3RT1016-1JB41-ZW97?","answer":"The 3RT1015-1BB42 is a size S00 contactor from the same SIRIUS family, but it uses a 24 V AC coil instead of the 24 V DC coil on this part. The DC coil with integrated diode suppression on the -ZW97 variant means it will not drop into an AC-coil circuit without rewiring the control voltage. For a DC-coil replacement, the 3RT1016-1AN22 uses a different coil voltage and the 3RT1016-2AP02 adds a different auxiliary contact block configuration."},{"question":"What is the depth of the 3RT1016-1JB41-ZW97?","answer":"The depth is 72 mm, width is 45 mm, and height is 57.5 mm. It mounts on 35 mm DIN rail with 6 mm side clearance required."},{"question":"What wire sizes does the 3RT1016-1JB41-ZW97 accept?","answer":"The screw terminals accept 2x (0.5 to 1.5 mm²) solid, 2x (0.75 to 2.5 mm²) stranded, or up to 1x 12 AWG conductors for the main circuit."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1016-1JB41-ZW97","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1016-1JB41-ZW97 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}