{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1016-1JB41-ZW98","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1016-1JB41-ZW98","canonicalUrl":"https://aoctrl.com/siemens/3RT1016-1JB41-ZW98","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1016-1JB41-ZW98","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, Size S00, 3RT1016-1JB41-ZW98, 24 VDC coil with integrated diode suppression, screw terminals, 45 mm width, snap-on DIN rail mounting.","salesMarkdown":"A built-in diode handles surge suppression across the coil, which saves an external flyback diode on the panel wiring. For motor duty, the key numbers are the AC-2 and AC-4 ratings at 400 V: 4 kW in AC-2 (slip-ring motor starting) and 8.5 A in AC-4 (plugging / inching duty). At higher line voltages the part delivers 4.5 kW at 500 V and 5.5 kW at 690 V — useful for 690 V industrial networks common in mining or marine installations. The auxiliary contact block is a single-pole instantaneous contact (1 NO or 1 NC depending on wiring). For applications needing more feedback, an add-on block is required — the base unit carries only one. These fuse ratings set the upstream protection sizing — don't oversize the branch fuse beyond 35 A gG if the contactor must survive a fault. Terminals accept solid or stranded copper: 2x 0.5–1.5 mm², 2x 0.75–2.5 mm², or max 2x 0.75–4 mm². AWG equivalents are 2x 20–16, 2x 18–14, and 1x 12. ## Environmental limits and approvals","metaTitle":"Siemens 3RT1016-1JB41-ZW98 SIRIUS Power Contactor, Size S00,","metaDescription":"Siemens SIRIUS 3RT1016-1JB41-ZW98 power contactor, Size S00, 24 VDC coil with diode. Rated 4.5 kW at 500 V, 5.5 kW at 690 V. In current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"57.5 mm","Maximum":"2 000 m","At The Side":"6 mm","Rated Value":"24 V","On The Front":"IP20","Initial Value":"0.7","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Full-scale value":"1.25","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 500 V rated value":"4.5 kW","at 690 V rated value":"5.5 kW","Instantaneous Contact":"1","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","at AC-2 at 400 V rated value":"4 kW","at AC-4 at 400 V rated value":"8.5 A","Design of the surge suppressor":"with diode","Closing power of magnet coil at DC":"2.3 W","Holding power of magnet coil at DC":"2.3 W","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"screw-type terminals","at ambient temperature 40 °C rated value":"22 A","Type of voltage of the control supply voltage":"DC","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=472342&mlfb=3RT1016-1JB41-ZW98","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1016-1JB41-ZW98/alternatives.json"},"ai":{"faq":[{"question":"What are the key motor ratings for 3RT1016-1JB41-ZW98?","answer":"At 400 V AC-2 duty it is rated 4 kW; at AC-4 duty it is rated 8.5 A. At 500 V it delivers 4.5 kW, and at 690 V it delivers 5.5 kW. These are the figures that determine whether the contactor is sized correctly for a given motor."},{"question":"Where can I buy 3RT1016-1JB41-ZW98 and get current pricing?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an inquiry for a firm price and lead time."},{"question":"Will 3RT1016-1JB41-ZW98 drop into a panel wired for 3RT1016-1AR11?","answer":"Both are Size S00 contactors on the same 45 mm DIN-rail footprint, so the mechanical fit is identical. The main difference is the coil voltage — the -1JB41 variant uses 24 VDC with diode suppression, while the -1AR11 uses a different coil voltage. Check coil compatibility before swapping."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1016-1JB41-ZW98","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1016-1JB41-ZW98 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}