{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1016-1TP02","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1016-1TP02","canonicalUrl":"https://aoctrl.com/siemens/3RT1016-1TP02","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1016-1TP02","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S00, 24 VDC coil, 10 A rated, screw-type terminals, 45 mm wide, 72 mm deep.","salesMarkdown":"The AC-4 rating at 400 V is 8.5 A — that's the switching capacity for reversing or inching duty where the contactor makes and breaks motor current under load. The contactor is rated for operation at altitudes up to 2,000 m without derating, and the operating temperature range is -25 to +60 °C. The width is 45 mm and depth is 72 mm, so it occupies a single 45 mm slot on the rail. The front face is rated IP20, meaning finger-safe but not protected against moisture ingress. This class of contactor is used in motor control centers, pump panels, conveyor drives, and general switching of resistive or inductive loads up to 5.5 kW at 690 V (AC-3 duty).","metaTitle":"Siemens 3RT1016-1TP02 SIRIUS Power Contactor, Size S00, 24 V","metaDescription":"Siemens SIRIUS 3RT1016-1TP02 power contactor, size S00, 24 VDC coil, 10 A rated, screw terminals, varistor suppression, current lifecycle stage. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"57.5 mm","Maximum":"2 000 m","at 50 Hz":"0.8 ... 1.1","at 60 Hz":"0.85 ... 1.1","At The Side":"6 mm","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"230 V","at 500 V rated value":"4.5 kW","at 60 Hz rated value":"230 V","at 690 V rated value":"5.5 kW","Instantaneous Contact":"0","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","at AC-2 at 400 V rated value":"4 kW","at AC-4 at 400 V rated value":"8.5 A","Design of the surge suppressor":"with varistor","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"screw-type terminals","at ambient temperature 40 °C rated value":"22 A","Apparent holding power of magnet coil at AC":"4.4 V·A","Apparent pick-up power of magnet coil at AC":"27 V·A","Type of voltage of the control supply voltage":"AC","Inductive power factor with closing power of the coil":"0.8","Inductive power factor with the holding power of the coil":"0.27","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=248764&mlfb=3RT1016-1TP02","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1016-1TP02/alternatives.json"},"ai":{"faq":[{"question":"What is the depth of this contactor?","answer":"The depth is 72 mm, with a width of 45 mm and height of 57.5 mm. It mounts on a 35 mm DIN rail."},{"question":"What are the wire size ranges for the main terminals?","answer":"The screw terminals accept 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or max. 2x (0.75 to 4 mm²) solid or stranded conductors. For AWG, that's 2x (20 to 16), 2x (18 to 14), or 1x 12."},{"question":"Does this contactor have built-in surge suppression?","answer":"Yes, it includes a varistor surge suppressor across the coil, so no external snubber is needed for the 24 VDC coil."},{"question":"What fuse rating is required for type 2 coordination?","answer":"For type 2 coordination (no-weld after short circuit), the required upstream fuse is gL/gG 20 A."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1016-1TP02","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1016-1TP02 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}