{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1016-2AM22","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1016-2AM22","canonicalUrl":"https://aoctrl.com/siemens/3RT1016-2AM22","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1016-2AM22","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S00, 24 VDC coil, spring-loaded terminals, 45 mm width, IP20 front.","salesMarkdown":"The coil holds at 24 VDC nominal; dropout is below 18 V, so you get a clean break on undervoltage without chatter. The 10 A rating at 24 V is for DC-12 / resistive loads at that voltage — handy for control circuits or small DC bus switching. For motor duty, the AC-3 rating at 400 V is the one that matters: 4 kW, which covers a standard 5.5 HP motor at 460 V (derated slightly). The 4.5 kW at 500 V and 5.5 kW at 690 V tell you this contactor is comfortable on 480 V and 600 V class systems as well. The 45 mm width is the S00 footprint — fits alongside other SIRIUS components on the same rail. Side-by-side mounting is allowed, but keep the 6 mm side clearance for airflow if you're packing them tight. The spring-loaded terminals accept 2x (0.25 to 2.5 mm²) solid or stranded, or 2x (24 to 14 AWG). Strip length is 8 mm; no ferrule needed for solid, but ferruled stranded is cleaner for maintenance pulls.","metaTitle":"Siemens 3RT1016-2AM22 SIRIUS Contactor, S00, 24 VDC Coil","metaDescription":"Siemens 3RT1016-2AM22 SIRIUS power contactor, size S00, 24 VDC coil, spring-loaded terminals. Rated 10 A at 24 V, 4.5 kW at 500 V. Current production. RFQ for lead time.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"73 mm","Solid":"2x (0.25 ... 2.5 mm²)","Width":"45 mm","Height":"60 mm","Maximum":"2 000 m","at 50 Hz":"0.8 ... 1.1","at 60 Hz":"0.85 ... 1.1","At The Side":"6 mm","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"208 V","at 500 V rated value":"4.5 kW","at 60 Hz rated value":"208 V","at 690 V rated value":"5.5 kW","Instantaneous Contact":"0","Side-by-side mounting":"Yes","For Main Current Circuit":"spring-loaded terminals","Single Or Multi-Stranded":"2x (0,25 ... 2,5 mm²)","at AC-2 at 400 V rated value":"4 kW","at AC-4 at 400 V rated value":"8.5 A","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (24 ... 14)","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.25 ... 1.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (24 ... 14)","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"spring-loaded terminals","at ambient temperature 40 °C rated value":"22 A","Apparent holding power of magnet coil at AC":"4.4 V·A","Apparent pick-up power of magnet coil at AC":"27 V·A","Finely Stranded Without Core End Processing":"2x (0.25 ... 2.5 mm²)","Type of voltage of the control supply voltage":"AC","Inductive power factor with closing power of the coil":"0.8","Inductive power factor with the holding power of the coil":"0.27","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=467892&mlfb=3RT1016-2AM22","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1016-2AM22/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional second-source to the 3RT1016-2AM22?","answer":"The 3RT1016-2AP02 is the closest peer — same S00 frame, same 24 VDC coil, but with screw terminals instead of spring-loaded. If your panel is wired for screw terminals, the 3RT1016-2AP02 drops in without rewiring; if you're specced for spring-loaded, stick with the 2AM22."},{"question":"What are the key electrical ratings for the 3RT1016-2AM22?","answer":"Rated for 10 A at 24 V DC-12, 4 kW at 400 V AC-3, 4.5 kW at 500 V, 5.5 kW at 690 V. The AC-4 rating is 8.5 A at 400 V. Coil is 24 VDC."},{"question":"What compliance documentation is available for the 3RT1016-2AM22?","answer":"As a Siemens SIRIUS industrial control component, it carries CE marking for the European market and is designed to meet IEC/EN 60947-4-1. RoHS and REACH compliance declarations are available from Siemens directly."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1016-2AM22","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1016-2AM22 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}