{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1016-2JC41","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1016-2JC41","canonicalUrl":"https://aoctrl.com/siemens/3RT1016-2JC41","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1016-2JC41","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S00, 3RT1016-2JC41, 24 VDC coil with integrated diode suppression, spring-loaded terminals, 10 A AC-12, 4.5 kW at 500 V, 5.5 kW at 690 V.","salesMarkdown":"For motor duty, the AC-2 rating of 4 kW at 400 V covers wound-rotor motors; the AC-4 rating of 8.5 A at 400 V covers plugging and inching duty. The 24 VDC coil draws 2.3 W both closing and holding, so the control transformer sizing is straightforward — no inrush spike beyond the steady-state power. The integrated diode means you don't need an external flyback diode across the coil, but verify polarity: the diode is reverse-biased when the coil is energized, so reversing the 24 VDC supply will short the diode. The 45 mm width and 60 mm height fit the S00 footprint — three or four of these side-by-side (side-by-side mounting is supported) fill a standard 200 mm DIN rail segment.","metaTitle":"Siemens SIRIUS 3RT1016-2JC41 Power Contactor, S00, 24 VDC Co","metaDescription":"Siemens SIRIUS 3RT1016-2JC41 power contactor, size S00, 24 VDC coil, spring-loaded terminals, 10 A AC-12, 4.5 kW at 500 V. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"73 mm","Solid":"2x (0.25 ... 2.5 mm²)","Width":"45 mm","Height":"60 mm","Maximum":"2 000 m","At The Side":"6 mm","Rated Value":"30 V","On The Front":"IP20","Initial Value":"0.7","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Full-scale value":"1.25","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 500 V rated value":"4.5 kW","at 690 V rated value":"5.5 kW","Instantaneous Contact":"1","Side-by-side mounting":"Yes","For Main Current Circuit":"spring-loaded terminals","Single Or Multi-Stranded":"2x (0,25 ... 2,5 mm²)","at AC-2 at 400 V rated value":"4 kW","at AC-4 at 400 V rated value":"8.5 A","Design of the surge suppressor":"with diode","Closing power of magnet coil at DC":"2.3 W","Holding power of magnet coil at DC":"2.3 W","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (24 ... 14)","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.25 ... 1.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (24 ... 14)","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"spring-loaded terminals","at ambient temperature 40 °C rated value":"22 A","Finely Stranded Without Core End Processing":"2x (0.25 ... 2.5 mm²)","Type of voltage of the control supply voltage":"DC","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=74308&mlfb=3RT1016-2JC41","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1016-2JC41/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional alternative to 3RT1016-2JC41?","answer":"The 3RT1016-2AP02 is a peer in the same S00 frame but uses an AC coil (230 V 50/60 Hz) instead of the 24 VDC coil with diode suppression. The 3RT1016-2JC41's spring-loaded terminals and DC coil with integrated diode are the key differences — if your control voltage is 24 VDC and you want tool-less wiring, stick with the 2JC41."},{"question":"Will 3RT1016-2JC41 drop into a panel specified for 3RT1016-2AP02?","answer":"Yes, the mounting footprint is identical — both are size S00, 45 mm wide, snap onto 35 mm DIN rail. The wiring difference is the coil supply: the 2JC41 needs 24 VDC, while the 2AP02 uses 230 VAC. If the panel already has a 24 VDC supply, the 2JC41 drops in without rewiring the main power circuit."},{"question":"Where can I buy 3RT1016-2JC41 and how is it quoted?","answer":"This part is sourced and quoted to order through independent distribution channels. Submit an RFQ for current pricing and availability — lead time and stock are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1016-2JC41","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1016-2JC41 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}