{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1017-1AB01-ZW95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1017-1AB01-ZW95","canonicalUrl":"https://aoctrl.com/siemens/3RT1017-1AB01-ZW95","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1017-1AB01-ZW95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S00, 3RT1017-1AB01-ZW95, 45 mm width, 5.5 kW at 400 V AC-3, screw terminals, IP20 front.","salesMarkdown":"The AC-3 rating at 400 V delivers 5.5 kW, which covers typical three-phase induction motors up to that output; the AC-4 rating at 400 V is 8.5 A, relevant for reversing or inching duty where the contacts break full-load current. The AC-4 rating of 8.5 A at 400 V is lower because that duty class involves breaking stalled-rotor current; if your application cycles the motor under load (plugging, inching), the AC-4 number governs the real contact life. The mechanical life of 30 million cycles means the actuator itself will outlast most electrical wear in normal use. This contactor is built for a panel environment: IP20 on the front and at the terminals means finger-safe against accidental contact, but it needs an enclosure for washdown or outdoor use. The screw-type terminals on the main circuit accept 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or up to 2x (0.75 to 4 mm²) solid or stranded — typical for the control wiring in a motor starter cell. Side-by-side mounting is allowed with a 6 mm gap between units for heat dissipation, so you can pack several contactors on a rail without derating, provided the ambient stays within -25 to +60 °C. The altitude limit of 2000 m is standard for non-derated operation; above that, the air density drop reduces the arc-quenching capability.","metaTitle":"Siemens 3RT1017-1AB01-ZW95 SIRIUS Power Contactor, S00, 5.5","metaDescription":"Siemens SIRIUS 3RT1017-1AB01-ZW95 power contactor, size S00, 45 mm wide, rated 5.5 kW at 400 V AC-2/AC-3. Current lifecycle stage. DIN rail mount. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"57.5 mm","Maximum":"2 000 m","at 50 Hz":"0.8 ... 1.1","at 60 Hz":"0.85 ... 1.1","At The Side":"6 mm","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"24 V","at 500 V rated value":"5.5 kW","at 60 Hz rated value":"24 V","at 690 V rated value":"5.5 kW","Instantaneous Contact":"1","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","at AC-2 at 400 V rated value":"5.5 kW","at AC-4 at 400 V rated value":"8.5 A","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"screw-type terminals","at ambient temperature 40 °C rated value":"22 A","Apparent holding power of magnet coil at AC":"4.4 V·A","Apparent pick-up power of magnet coil at AC":"27 V·A","Type of voltage of the control supply voltage":"AC","Inductive power factor with closing power of the coil":"0.8","Inductive power factor with the holding power of the coil":"0.27","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=94194&mlfb=3RT1017-1AB01-ZW95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1017-1AB01-ZW95/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional second-source — 3RT1017-1AP01?","answer":"The 3RT1017-1AP01 is a sibling in the same S00 frame with the same 5.5 kW AC-3 rating at 400 V. The difference is typically the coil voltage or auxiliary contact configuration; verify your coil voltage and aux contact count before substituting."},{"question":"What is the depth of this contactor?","answer":"The depth is 72 mm, which fits standard DIN-rail enclosures with that clearance."},{"question":"What wire sizes does the screw terminal accept?","answer":"The screw terminals accept 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or up to 2x (0.75 to 4 mm²) solid or stranded conductors, plus 2x (20 to 16), 2x (18 to 14), or 1x 12 AWG."},{"question":"Will 3RT1017-1AB01-ZW95 drop into a panel specified around 3RT1017-1AP01 without rewiring?","answer":"The S00 frame size and 45 mm width are identical, so the mechanical footprint matches. The coil voltage and auxiliary contact configuration may differ — check the coil rating (24 V at 50/60 Hz for this variant) and aux contact count before assuming a drop-in replacement."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1017-1AB01-ZW95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1017-1AB01-ZW95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}