{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1017-1AD01-1AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1017-1AD01-1AA0","canonicalUrl":"https://aoctrl.com/siemens/3RT1017-1AD01-1AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1017-1AD01-1AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, Size S00, 3RT1017-1AD01-1AA0, 45 mm width, 10 A at 24 V DC, screw terminals, IP20 front protection.","salesMarkdown":"## SIRIUS Size S00 Power Contactor — 3RT1017-1AD01-1AA0 It carries a 10 A rated operational current at 24 V DC and 5.5 kW at 400 V in AC-3 duty, making it suited for small-to-medium induction motors on conveyors, pumps, and fans. The 45 mm wide body snaps onto a 35 mm DIN rail per EN 50022, and the screw-type terminals accept conductors from 0.5 to 4 mm². The AC-3 rating at 400 V (5.5 kW) is the figure that governs motor switching — it tells you this contactor can handle a standard 5.5 kW induction motor across the line. The AC-1 resistive rating at 400 V (3 A) covers heater or lighting loads where inrush is minimal. For DC switching, the 24 V DC rating of 10 A drops to 0.3 A at 220 V DC due to arc extinction limits in DC circuits — factor that into any DC load schedule. Pollution degree 3 (industrial environment with conductive or dry non-conductive pollution) and a -25 to +60 °C operating range mean this contactor is rated for unheated enclosures and typical factory-floor conditions. The mechanical endurance of 30 million operations exceeds the electrical endurance by a wide margin — in practice, the electrical life under load (not stated here) will be lower, but the mechanical figure confirms the contactor is built for high-cycle applications like packaging or material handling where the coil cycles frequently. The 72 mm depth leaves clearance for wiring ducts and busbar systems. The screw-type terminals accept 2 x (0.5 to 1.5 mm²), 2 x (0.75 to 2.5 mm²), or up to 2 x (0.75 to 4 mm²) — the larger cross-section is for power-in and power-out, while the smaller range suits control wiring. AWG equivalents are 2 x (20 to 16), 2 x (18 to 14), and 1 x 12. The 6 mm side clearance to adjacent components is the minimum for heat dissipation; no additional gap is required when using the side-by-side mounting feature.","metaTitle":"Siemens 3RT1017-1AD01-1AA0 SIRIUS Power Contactor, Size S00,","metaDescription":"Siemens SIRIUS 3RT1017-1AD01-1AA0 power contactor, Size S00, 45 mm width, 10 A at 24 V DC, screw terminals, IP20, current lifecycle stage, available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"57.5 mm","Maximum":"2 000 m","at 50 Hz":"0.8 ... 1.1","at 60 Hz":"0.85 ... 1.1","At The Side":"6 mm","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"42 V","at 500 V rated value":"5.5 kW","at 60 Hz rated value":"42 V","at 690 V rated value":"5.5 kW","Instantaneous Contact":"1","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","at AC-2 at 400 V rated value":"5.5 kW","at AC-4 at 400 V rated value":"8.5 A","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"screw-type terminals","at ambient temperature 40 °C rated value":"22 A","Apparent holding power of magnet coil at AC":"4.4 V·A","Apparent pick-up power of magnet coil at AC":"27 V·A","Type of voltage of the control supply voltage":"AC","Inductive power factor with closing power of the coil":"0.8","Inductive power factor with the holding power of the coil":"0.27","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=219648&mlfb=3RT1017-1AD01-1AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1017-1AD01-1AA0/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1017-1AD01-1AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1017-1AD01-1AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}