{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1017-1AD02","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1017-1AD02","canonicalUrl":"https://aoctrl.com/siemens/3RT1017-1AD02","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1017-1AD02","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT1017-1AD02, size S00 power contactor, 24 V 50/60 Hz coil, screw terminals, 10 A AC-1, 5.5 kW AC-3 at 400 V, IP20, DIN rail mount.","salesMarkdown":"The 24 V 50/60 Hz coil pulls in reliably across the full rated voltage range (0.8–1.1 x Us at 50 Hz, 0.85–1.1 at 60 Hz) and holds without chatter down to the dropout threshold. AC-3 duty at 400 V carries 5.5 kW — sized for a standard 7.5 hp motor at that voltage. AC-4 reversing or plugging service is rated 8.5 A at 400 V, so expect some derating if the application cycles hard. Side-by-side mounting is permitted, so multiple units pack tight on the rail without derating the thermal capacity. The headline AC-1 rating of 10 A at 24 V tells you the resistive switching capacity — heaters, lighting banks, or transformer primaries. AC-4 at 8.5 A is the figure to watch if the contactor sees inching or reversing duty; that's the wear-and-tear number that drives contact life. The mechanical life of 30 million operations is typical for S00 — the electrical life will be lower and depends on the switching category and load current. That's the selectivity data a panel designer needs for the upstream protection scheme. The enclosure is IP20 on the front and at the terminals — suitable for a clean, dry cabinet. Compliance documentation includes RoHS and REACH substance prohibitance dated July 1, 2006, covering the standard EU directives. ## Panel integration The 45 mm width and 57.5 mm height on a 72 mm depth footprint means it occupies a standard 2.5-module width on the DIN rail. Screw terminals are accessible from the front; the IP20 rating means no finger-safe covers are required inside a locked cabinet. Side-by-side mounting without gaps saves rail space when grouping multiple contactors for a motor control center.","metaTitle":"Siemens 3RT1017-1AD02 SIRIUS Contactor, S00, 24V 50/60Hz, 10","metaDescription":"Siemens SIRIUS 3RT1017-1AD02 power contactor, size S00, 24V 50/60Hz coil, 10A AC-1, 5.5kW AC-3 at 400V. Screw terminals, IP20, DIN rail. Active lifecycle, sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"57.5 mm","at 50 Hz":"0.8 ... 1.1","at 60 Hz":"0.85 ... 1.1","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Size Of Contactor":"S00","Solid Or Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","Product Brand Name":"SIRIUS","Degree Of Pollution":"3","Product Designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"42 V","at 500 V rated value":"5.5 kW","at 60 Hz rated value":"42 V","at 690 V rated value":"5.5 kW","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","at AC-2 at 400 V rated value":"5.5 kW","at AC-4 at 400 V rated value":"8.5 A","Substance Prohibitance (Date)":"01.07.2006 00:00:00","at AWG cables for main contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","For Auxiliary And Control Circuit":"screw-type terminals","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","reference code acc. to IEC 81346-2":"Q","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","operational current at AC-12 maximum":"10 A","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","apparent holding power of magnet coil at AC":"4.4 V·A","apparent pick-up power of magnet coil at AC":"27 V·A","Type Of Voltage Of The Control Supply Voltage":"AC","Required Spacing For Grounded Parts At The Side":"6 mm","Inductive Power Factor With Closing Power Of The Coil":"0.8","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Inductive Power Factor With The Holding Power Of The Coil":"0.27","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"1","number of NO contacts for auxiliary contacts instantaneous contact":"0","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=361857&mlfb=3RT1017-1AD02","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1017-1AD02/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1017-1AD02","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1017-1AD02 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}