{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1017-1AD02-1AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1017-1AD02-1AA0","canonicalUrl":"https://aoctrl.com/siemens/3RT1017-1AD02-1AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1017-1AD02-1AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS S00 power contactor, 3RT1017-1AD02-1AA0, 5.5 kW at 500 V AC-3, 8.5 A AC-4, screw terminals, snap-on 35 mm DIN rail, IP20 front.","salesMarkdown":"The Siemens 3RT1017-1AD02-1AA0 is a SIRIUS S00 power contactor — the smallest frame in the SIRIUS family, sized for motor loads up to 5.5 kW at 500 V in AC-3 duty and rated 8.5 A in AC-4 for reversing or plugging service. The S00 footprint — 45 mm wide, 57.5 mm tall, 72 mm deep — fits tightly on a DIN rail; six millimeters of side clearance is all it needs between units. The 8.5 A AC-4 figure matters if the contactor sees inching, jogging, or plug-reverse duty, where the contacts break full motor current at standstill. For resistive or fan loads, the AC-12 maximum operating current is 10 A. The coil draws 0.8 to 1.1 A at 50 Hz and 0.85 to 1.1 A at 60 Hz — a standard 24 V control transformer handles that without oversizing. Type 1 coordination requires a 35 A gL/gG fuse upstream; Type 2 coordination needs a 20 A gL/gG fuse. That's the fuse size a maintenance tech writes into the panel schedule, not a guess. ## Terminal and environmental fit Main circuit terminals accept 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or up to 2x (0.75 to 4 mm²) solid or stranded copper — covers the wire sizes typical for a 5.5 kW motor circuit. AWG equivalents are 2x (20 to 16), 2x (18 to 14), and 1x 12. Front and terminal protection is IP20 — finger-safe for a panel environment but not rated for washdown.","metaTitle":"Siemens 3RT1017-1AD02-1AA0 SIRIUS S00 Power Contactor, 5.5 k","metaDescription":"Siemens SIRIUS 3RT1017-1AD02-1AA0 S00 power contactor, 5.5 kW at 500 V AC-3, 8.5 A AC-4. Current production. DIN rail mount, IP20. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"57.5 mm","Maximum":"2 000 m","at 50 Hz":"0.8 ... 1.1","at 60 Hz":"0.85 ... 1.1","At The Side":"6 mm","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"42 V","at 500 V rated value":"5.5 kW","at 60 Hz rated value":"42 V","at 690 V rated value":"5.5 kW","Instantaneous Contact":"0","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","at AC-2 at 400 V rated value":"5.5 kW","at AC-4 at 400 V rated value":"8.5 A","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"screw-type terminals","at ambient temperature 40 °C rated value":"22 A","Apparent holding power of magnet coil at AC":"4.4 V·A","Apparent pick-up power of magnet coil at AC":"27 V·A","Type of voltage of the control supply voltage":"AC","Inductive power factor with closing power of the coil":"0.8","Inductive power factor with the holding power of the coil":"0.27","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=412830&mlfb=3RT1017-1AD02-1AA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1017-1AD02-1AA0/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional second-source for 3RT1017-1AD02-1AA0?","answer":"The 3RT1016-2AP02 is a peer in the same S00 frame but with different coil voltage and terminal configuration — it will not drop into the same panel without checking the coil rating and wiring plan."},{"question":"Where can I buy 3RT1017-1AD02-1AA0 and get current pricing?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer."},{"question":"What is the depth of 3RT1017-1AD02-1AA0?","answer":"The depth is 72 mm, measured from the DIN rail mounting surface to the front of the housing."},{"question":"What wire sizes does the main terminal accept?","answer":"The screw terminals accept 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or up to 2x (0.75 to 4 mm²) solid or stranded copper; AWG equivalents are 2x (20 to 16), 2x (18 to 14), and 1x 12."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1017-1AD02-1AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1017-1AD02-1AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}