{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1017-1AH02","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1017-1AH02","canonicalUrl":"https://aoctrl.com/siemens/3RT1017-1AH02","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1017-1AH02","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS S00 power contactor, 3RT1017-1AH02, 5.5 kW at 400 V AC-3, 24 VDC coil, screw terminals, IP20, DIN rail mount.","salesMarkdown":"The 3RT1017-1AH02: The 5.5 kW at 400 V AC-3 rating is the headline motor-switching capacity — it drives a standard 4-pole induction motor up to that load. The 24 VDC coil draws the listed holding current; verify your control transformer and rectifier can supply the inrush without dropout. Type 2 coordination (no-weld fault clearing) requires a 20 A gL/gG fuse upstream per the spec. Type 1 coordination allows a 35 A gL/gG fuse. The S00 frame is 45 mm wide, 57.5 mm tall, and 72 mm deep — a compact footprint that fits tightly packed DIN-rail panels. Finger-safe IP20 protection on the front and terminals means it can be installed in open panels without additional shrouding.","metaTitle":"Siemens 3RT1017-1AH02 SIRIUS Power Contactor, 5.5 kW at 400","metaDescription":"Siemens 3RT1017-1AH02 SIRIUS S00 power contactor, 5.5 kW at 400 V AC-3, 24 VDC coil, screw terminals, IP20, DIN rail mount. Current lifecycle stage. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"57.5 mm","at 50 Hz":"0.8 ... 1.1","at 60 Hz":"0.85 ... 1.1","At The Side":"6 mm","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","Mounting Type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Size Of Contactor":"S00","Product Brand Name":"SIRIUS","Degree Of Pollution":"3","Product Designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 400 V rated value":"5.5 kW","at 50 Hz rated value":"48 V","at 500 V rated value":"5.5 kW","at 60 Hz rated value":"48 V","at 690 V rated value":"5.5 kW","Instantaneous Contact":"0","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","at AC-2 at 400 V rated value":"5.5 kW","at AC-4 at 400 V rated value":"8.5 A","For Auxiliary And Control Circuit":"screw-type terminals","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","operating current at AC-12 maximum":"10 A","at AWG conductors for main contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","reference code acc. to DIN EN 81346-2":"Q","Fastening Method Side-By-Side Mounting":"Yes","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","at ambient temperature 40 °C rated value":"22 A","apparent holding power of magnet coil at AC":"4.4 V·A","apparent pick-up power of magnet coil at AC":"27 V·A","Type Of Voltage Of The Control Supply Voltage":"AC","operating current at AC-15 at 400 V rated value":"3 A","operational current at AC-15 at 230 V rated value":"6 A","Inductive Power Factor With Closing Power Of The Coil":"0.8","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Inductive Power Factor With The Holding Power Of The Coil":"0.27","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000","type of connectable conductor cross-sections at AWG conductors for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=364213&mlfb=3RT1017-1AH02","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1017-1AH02/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3RT1017-1AH02?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ to receive current pricing and availability confirmed at quote time."},{"question":"What is 3RT1017-1AH02's listed depth?","answer":"The listed depth is 72 mm, with a width of 45 mm and height of 57.5 mm for the S00 frame."},{"question":"What compliance documentation does this brand provide for 3RT1017-1AH02?","answer":"The product carries the SIRIUS brand designation. Standard Siemens documentation for this series includes RoHS and REACH declarations; UL, CSA, and CE approvals are typical for the SIRIUS contactor family, though specific certification marks for this order code should be verified against the nameplate or manufacturer documentation."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1017-1AH02","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1017-1AH02 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}