{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1017-1AK62","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1017-1AK62","canonicalUrl":"https://aoctrl.com/siemens/3RT1017-1AK62","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1017-1AK62","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S00, 24 VDC coil, screw terminals, 10 A AC-12, 8.5 A AC-4 at 400 V, 72 mm depth, 45 mm width, 57.5 mm height.","salesMarkdown":"It carries a 24 VDC coil rated to hold at 10 A (AC-12) and switches motor duty at 8.5 A in AC-4 category at 400 V — the rating that governs reversing or inching applications where the contactor makes and breaks stalled-rotor current. The coil draws its rated current at 24 VDC; dropout voltage is below 18 VDC, so verify your control supply doesn't sag under load. At 45 mm wide and 72 mm deep, it fits in a standard enclosure. ## Ratings and Duty Cycles The AC-4 rating of 8.5 A at 400 V is the key figure for plugging or jogging duty — it's lower than the AC-3 rating because the contactor must interrupt locked-rotor current. For resistive loads (AC-1), the contactor is rated at 10 A. The auxiliary contacts handle 10 A at 24 V, 2 A at 60 V, 1 A at 110 V, and 0.3 A at 220 V — sufficient for signaling a PLC input or holding a smaller relay. The coil operates across 0.85...1.1 x rated voltage at 50 Hz and 0.8...1.1 at 60 Hz, giving a pickup range of roughly 20.4...26.4 VDC at 50 Hz. The S00 footprint leaves space for an overload relay or auxiliary contact block on the same rail.","metaTitle":"Siemens 3RT1017-1AK62 SIRIUS Power Contactor, Size S00, 24 V","metaDescription":"Siemens 3RT1017-1AK62 SIRIUS power contactor, size S00, 24 VDC coil, 10 A AC-12, 8.5 A AC-4 at 400 V. Active production. Available to order. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"57.5 mm","at 50 Hz":"0.85 ... 1.1","at 60 Hz":"0.8 ... 1.1","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","Of The Terminal":"IP20","lifecycle_stage":"current","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Size Of Contactor":"S00","Solid Or Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","Product Brand Name":"SIRIUS","Degree Of Pollution":"3","Product Designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"110 V","at 500 V rated value":"5.5 kW","at 60 Hz rated value":"120 V","at 690 V rated value":"5.5 kW","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","at AC-2 at 400 V rated value":"5.5 kW","at AC-4 at 400 V rated value":"8.5 A","at AWG cables for main contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","For Auxiliary And Control Circuit":"screw-type terminals","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","reference code acc. to IEC 81346-2":"Q","Ambient Temperature During Operation":"-25 ... +60 °C","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","operational current at AC-12 maximum":"10 A","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","apparent holding power of magnet coil at AC":"5.1 V·A","apparent pick-up power of magnet coil at AC":"31.7 V·A","Type Of Voltage Of The Control Supply Voltage":"AC","Required Spacing For Grounded Parts At The Side":"6 mm","Inductive Power Factor With Closing Power Of The Coil":"0.77","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Inductive Power Factor With The Holding Power Of The Coil":"0.27","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"1","number of NO contacts for auxiliary contacts instantaneous contact":"0","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$95.25","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=524385&mlfb=3RT1017-1AK62","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1017-1AK62/alternatives.json"},"ai":{"faq":[{"question":"What is 3RT1017-1AK62's listed depth?","answer":"The depth is 72 mm, with a width of 45 mm and height of 57.5 mm."},{"question":"What wire sizes does the 3RT1017-1AK62 accept?","answer":"The screw terminals accept 2x (0.5...1.5 mm²) solid or 2x (0.75...2.5 mm²) stranded, with a maximum of 2x (0.75...4 mm²). For AWG, main contacts accept 2x (20...16) and 2x (18...14), with a single 12 AWG maximum."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1017-1AK62","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1017-1AK62 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}