{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1017-1AP08-0MA6","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1017-1AP08-0MA6","canonicalUrl":"https://aoctrl.com/siemens/3RT1017-1AP08-0MA6","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1017-1AP08-0MA6","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS, power contactor, size S00, 3RT1017-1AP08-0MA6, 24 VDC coil, 10 A rated operating current at AC-12, screw terminals, DIN rail mount.","salesMarkdown":"The screw-type terminals on the main current circuit accept 2x (0.5 to 1.5 mm²) solid or stranded, 2x (0.75 to 2.5 mm²), or up to 2x (0.75 to 4 mm²). For AWG, that is 2x (20 to 16) or 2x (18 to 14) or 1x 12. The terminal is rated IP20 — finger-safe once wired, but the front face of the contactor is also IP20, so it can sit in an open panel without an additional cover. ## Motor Switching and Duty Ratings For motor loads, the AC-2 rating at 400 V is 5.5 kW, and the AC-4 rating at 400 V is 8.5 A. At 500 V the motor power rating is 5.5 kW; at 690 V it is also 5.5 kW. The contactor is rated for both 50 Hz and 60 Hz operation, with the operating range spanning 0.8 to 1.1 times the rated voltage at 50 Hz and 0.85 to 1.1 at 60 Hz. The auxiliary contact block carries 10 A at 24 V, 2 A at 60 V, 1 A at 110 V, 0.3 A at 220 V, and 6 A at 230 V. That covers most PLC-level signal circuits and relay loads. For Type 2 coordination (contactor remains operational after a fault), the fuse is gL/gG 20 A. This is a standard distinction — Type 2 is what most panel builders specify for production lines where downtime matters. Mechanical endurance is typical 30 million operating cycles — that is the mechanical life before the contactor wears out, not the electrical life under load. Electrical life will be shorter and depends on the switching current and duty class. Same part, different passport — if you are comparing pricing across regions, this order code is the global Siemens part number. The 0MA6 suffix indicates a specific coil variant and auxiliary configuration; it is not a regional market code. Genuine is genuine regardless of which Siemens factory it came from.","metaTitle":"Siemens 3RT1017-1AP08-0MA6 SIRIUS Power Contactor, S00, 24 V","metaDescription":"Siemens SIRIUS 3RT1017-1AP08-0MA6 power contactor, size S00, 24 VDC coil, 10 A rated. Current production. DIN rail mount. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"114 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"57.5 mm","Maximum":"2 000 m","at 50 Hz":"0.8 ... 1.1","at 60 Hz":"0.85 ... 1.1","At The Side":"6 mm","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"230 V","at 500 V rated value":"5.5 kW","at 60 Hz rated value":"230 V","at 690 V rated value":"5.5 kW","Instantaneous Contact":"3","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","at AC-2 at 400 V rated value":"5.5 kW","at AC-4 at 400 V rated value":"8.5 A","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"screw-type terminals","at ambient temperature 40 °C rated value":"22 A","Apparent holding power of magnet coil at AC":"4.4 V·A","Apparent pick-up power of magnet coil at AC":"27 V·A","Type of voltage of the control supply voltage":"AC","Inductive power factor with closing power of the coil":"0.8","Inductive power factor with the holding power of the coil":"0.27","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=317301&mlfb=3RT1017-1AP08-0MA6","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1017-1AP08-0MA6/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional second-source to 3RT1017-1AP08-0MA6?","answer":"The 3RT1016-1AG61 is a smaller-frame S00 contactor with a different coil voltage (not 24 VDC) and lower ratings. It will not drop into the same panel without rewiring the coil circuit and checking the load current — they share the same DIN rail footprint and terminal layout, but the coil and power ratings differ. If you need a direct replacement, stick with the 3RT1017-1AP08-0MA6 or a same-frame sibling with the same coil voltage."},{"question":"What compliance documentation does Siemens provide for 3RT1017-1AP08-0MA6?","answer":"Siemens SIRIUS contactors carry CE marking for the European market and are designed to meet IEC/EN 60947-4-1. The manufacturer provides a declaration of conformity and technical file upon request. RoHS and REACH compliance is standard for current-production Siemens industrial controls, though the specific declaration should be requested at order time if your QA team requires it for incoming inspection."},{"question":"Where can I buy 3RT1017-1AP08-0MA6 and how is it quoted?","answer":"We source this current-production contactor to order against an RFQ. Send your target quantity and delivery window, and we will return a firm price and confirmed lead time. Availability and current pricing are confirmed at quote time — no stock count or price is listed here because the market moves daily."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1017-1AP08-0MA6","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1017-1AP08-0MA6 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}