{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1017-1AT62","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1017-1AT62","canonicalUrl":"https://aoctrl.com/siemens/3RT1017-1AT62","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1017-1AT62","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS, power contactor, 3RT1017-1AT62, size S00, 3 NO main contacts, 24 VDC coil, 10 A rated, screw terminals, IP20.","salesMarkdown":"It's a current-production part, so no lifecycle scramble; this is what you spec into a new panel or drop in as a line-down spare for an existing S00 footprint. ## Motor duty and coordination — the real selection numbers For AC-4 (plugging/reversing/inching) at 400 V, the rated operational current is 8.5 A. These are the numbers that govern contact life, not the 10 A AC-12 resistive rating. Type 1 coordination requires a 35 A gL/gG fuse; type 2 coordination needs a 20 A gL/gG fuse. If you're coordinating with a motor starter or overload relay, the 20 A type 2 limit is the one that keeps the contactor re-usable after a fault. Both main and auxiliary/control circuits use screw-type terminals. The main contacts accept 2x (0.5...1.5 mm²), 2x (0.75...2.5 mm²), or max 2x (0.75...4 mm²) solid or stranded — same ranges for the auxiliary contacts. AWG equivalents are 2x (20...16), 2x (18...14), and 1x 12. The 72 mm depth, 45 mm width, and 57.5 mm height fit a shallow backpanel. Storage temperature exceeds that range — the handling limit, not the running limit. RoHS compliance date is 01.07.2006, so it meets the original EU RoHS directive. Electrical life depends on the switching category and current; at AC-2 5.5 kW you'll get a fraction of that, but still well into the millions for most conveyor or pump cycling rates.","metaTitle":"Siemens 3RT1017-1AT62 SIRIUS Power Contactor, S00, 3 NO, 24","metaDescription":"Siemens SIRIUS 3RT1017-1AT62 power contactor, size S00, 3 NO main contacts, 24 VDC coil, 10 A rated, AC-2 5.5 kW at 400 V. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"57.5 mm","at 60 Hz":"0.8 ... 1.1","On The Front":"IP20","1 Rated Value":"60 Hz","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Size Of Contactor":"S00","Solid Or Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","Product Brand Name":"SIRIUS","Degree Of Pollution":"3","Product Designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 500 V rated value":"5.5 kW","at 60 Hz rated value":"600 V","at 690 V rated value":"5.5 kW","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","at AC-2 at 400 V rated value":"5.5 kW","at AC-4 at 400 V rated value":"8.5 A","Substance Prohibitance (Date)":"01.07.2006 00:00:00","at AWG cables for main contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","For Auxiliary And Control Circuit":"screw-type terminals","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","reference code acc. to IEC 81346-2":"Q","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","operational current at AC-12 maximum":"10 A","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","apparent holding power of magnet coil at AC":"5.1 V·A","apparent pick-up power of magnet coil at AC":"31.7 V·A","Type Of Voltage Of The Control Supply Voltage":"AC","Required Spacing For Grounded Parts At The Side":"6 mm","Inductive Power Factor With Closing Power Of The Coil":"0.77","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Inductive Power Factor With The Holding Power Of The Coil":"0.27","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"1","number of NO contacts for auxiliary contacts instantaneous contact":"0","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=73565&mlfb=3RT1017-1AT62","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1017-1AT62/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1017-1AT62","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1017-1AT62 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}