{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1017-1BB41-ZW96","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1017-1BB41-ZW96","canonicalUrl":"https://aoctrl.com/siemens/3RT1017-1BB41-ZW96","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1017-1BB41-ZW96","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT1017-1BB41-ZW96 power contactor, size S00, 24 V DC coil, screw-type terminals, IP20 front protection, 45 mm width.","salesMarkdown":"Rated for AC-3 duty at 5.5 kW on 400 V, it handles the inductive load of a standard three-phase motor up to that power. The same contactor also carries 10 A in AC-1 (resistive) service and 8.5 A in AC-4 (plugging/reversing) at 400 V. Pick-up voltage is 0.85 × rated (20.4 V DC); drop-out is 1.1 × rated (26.4 V DC). If your motor nameplate says 5.5 kW or less on a 400 V line, this contactor is electrically sized. At 500 V and 690 V, it also delivers 5.5 kW in AC-3. For DC switching, the contactor is rated 10 A at 24 V, 2 A at 60 V, 1 A at 110 V, and 0.3 A at 220 V — useful for interposing or pilot-duty circuits, but the inductive DC load curve is steeper than AC, so derate further for DC motor or solenoid loads. Short-circuit coordination is specified: Type 2 coordination requires a gL/gG fuse of 20 A; Type 1 coordination allows 35 A. This matters for selectivity studies and SCCR compliance in the panel. The one instantaneous auxiliary contact (1 NO/NC configurable) is built in, so no separate aux block is needed for basic feedback. The size S00 footprint (45 × 57.5 × 72 mm) is standard across the SIRIUS 3RT1 range. Main current circuit terminals are screw-type, accepting 2 × (0.5…1.5 mm²), 2 × (0.75…2.5 mm²), or max 2 × (0.75…4 mm²) solid/stranded, plus 1 × 12 AWG. The -ZW96 suffix indicates a special version, but the base electrical and mechanical ratings match the standard 3RT1017-1BB41. Verify the -ZW96 specifics with the order documentation if traceability to a particular project is required.","metaTitle":"Siemens 3RT1017-1BB41-ZW96 SIRIUS Power Contactor, Size S00,","metaDescription":"Siemens SIRIUS 3RT1017-1BB41-ZW96 power contactor, size S00, 24 VDC coil, screw terminals, IP20. Rated for AC-3 5.5 kW at 400 V. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"57.5 mm","Maximum":"2 000 m","At The Side":"6 mm","Rated Value":"24 V","On The Front":"IP20","Initial Value":"0.85","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Full-scale value":"1.1","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 500 V rated value":"5.5 kW","at 690 V rated value":"5.5 kW","Instantaneous Contact":"1","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","at AC-2 at 400 V rated value":"5.5 kW","at AC-4 at 400 V rated value":"8.5 A","Closing power of magnet coil at DC":"3.3 W","Holding power of magnet coil at DC":"3.3 W","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"screw-type terminals","at ambient temperature 40 °C rated value":"22 A","Type of voltage of the control supply voltage":"DC","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=471037&mlfb=3RT1017-1BB41-ZW96","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1017-1BB41-ZW96/alternatives.json"},"ai":{"faq":[{"question":"What wire sizes does the screw terminal accept?","answer":"The main circuit terminals accept 2 × (0.5…1.5 mm²), 2 × (0.75…2.5 mm²), or max 2 × (0.75…4 mm²) solid or stranded conductors, plus 1 × 12 AWG."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1017-1BB41-ZW96","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1017-1BB41-ZW96 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}