{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1017-1BB41-ZW98","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1017-1BB41-ZW98","canonicalUrl":"https://aoctrl.com/siemens/3RT1017-1BB41-ZW98","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1017-1BB41-ZW98","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT1017-1BB41-ZW98, size S00 power contactor, 24 VDC coil, 45 mm wide, screw terminals, IP20.","salesMarkdown":"The Siemens 3RT1017-1BB41-ZW98 is a SIRIUS power contactor in size S00, rated for switching motor loads up to 5.5 kW at 400 V AC (AC-3 duty) and 5.5 kW at 690 V. The 24 VDC coil draws 3.3 W holding power, with a pick-up threshold of 0.85 x rated voltage (20.4 V) and a drop-out of 0.1 x rated voltage (2.4 V), so it stays latched through typical supply dips but releases cleanly on undervoltage. For heavy-duty reversing or inching (AC-4), it carries 8.5 A at 400 V — a useful spec for conveyor or hoist applications where frequent starts under load are the norm. The DC switching capability at 24 V is 10 A, covering solenoid and small DC motor loads. The 45 mm width and 72 mm depth leave room for side-by-side mounting without derating, making it a dense fit in a standard panel enclosure. For type 1 coordination (no weld prevention, just no fire risk), use a 35 A gL/gG fuse upstream. For type 2 coordination (contactor remains operable after a fault), drop to a 20 A gL/gG fuse. This is the spec the panel designer needs to match the short-circuit rating of the MCC.","metaTitle":"Siemens 3RT1017-1BB41-ZW98 SIRIUS Power Contactor, 24 VDC, 4","metaDescription":"Siemens SIRIUS 3RT1017-1BB41-ZW98 power contactor, size S00, 24 VDC coil, 45 mm wide, 5.5 kW at 400 V, IP20. Active production, sourced to order via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"57.5 mm","Maximum":"2 000 m","At The Side":"6 mm","Rated Value":"24 V","On The Front":"IP20","Initial Value":"0.85","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Full-scale value":"1.1","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 500 V rated value":"5.5 kW","at 690 V rated value":"5.5 kW","Instantaneous Contact":"1","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","at AC-2 at 400 V rated value":"5.5 kW","at AC-4 at 400 V rated value":"8.5 A","Closing power of magnet coil at DC":"3.3 W","Holding power of magnet coil at DC":"3.3 W","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"screw-type terminals","at ambient temperature 40 °C rated value":"22 A","Type of voltage of the control supply voltage":"DC","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=354730&mlfb=3RT1017-1BB41-ZW98","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1017-1BB41-ZW98/alternatives.json"},"ai":{"faq":[{"question":"What are the key dimensions for panel layout?","answer":"Width is 45 mm, height 57.5 mm, depth 72 mm. It mounts on 35 mm DIN rail and can be installed side-by-side with other devices."},{"question":"What wire sizes does the main terminal accept?","answer":"Screw terminals accept 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or up to 2x (0.75 to 4 mm²) solid/stranded. For AWG: 2x (20 to 16), 2x (18 to 14), or 1x 12."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1017-1BB41-ZW98","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1017-1BB41-ZW98 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}