{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1017-1BD41","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1017-1BD41","canonicalUrl":"https://aoctrl.com/siemens/3RT1017-1BD41","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1017-1BD41","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S00, 3RT1017-1BD41, 24 VDC coil, screw-type terminals, IP20, 45 mm width, 5.5 kW at 400 V AC-3.","salesMarkdown":"The Siemens 3RT1017-1BD41 is a SIRIUS power contactor in the compact size S00 frame, with a 24 VDC solenoid coil drawing 3.3 W for both pick-up and hold. It is rated for motor switching in AC-3 duty up to 5.5 kW at 400 V, and carries the same power rating at 500 V and 690 V per the datasheet. The AC-3 rating of 5.5 kW at 400 V tells you this contactor handles a standard 3-phase induction motor up to that shaft power under starting conditions — the contacts are sized for the inrush and the breaking of the running load. For AC-4 duty (plugging, inching, reversing), the rated operational current is 8.5 A at 400 V, which is the figure to use when the motor sees frequent reversals or jogging. The DC coil consumes 3.3 W continuously, so the control transformer or PLC output needs to supply that without voltage drop below the 0.85 x 24 V pick-up threshold. This lets the panel builder size the branch protection correctly for the required selectivity. The screw terminals accept solid or stranded conductors: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), and up to 2x (0.75 to 4 mm²) maximum. AWG equivalents are 2x (20 to 16), 2x (18 to 14), and 1x 12. IP20 on the front and terminals means finger-safe but not protected against moisture — install inside a panel with at least IP54 enclosure.","metaTitle":"Siemens 3RT1017-1BD41 SIRIUS Power Contactor, Size S00, 24 V","metaDescription":"Siemens SIRIUS 3RT1017-1BD41 power contactor, size S00, 24 VDC coil, screw terminals, IP20. Rated for motor loads up to 5.5 kW at 400 V AC-3. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"57.5 mm","Maximum":"2 000 m","At The Side":"6 mm","Rated Value":"42 V","On The Front":"IP20","Initial Value":"0.85","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Full-scale value":"1.1","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 500 V rated value":"5.5 kW","at 690 V rated value":"5.5 kW","Instantaneous Contact":"1","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","at AC-2 at 400 V rated value":"5.5 kW","at AC-4 at 400 V rated value":"8.5 A","Closing power of magnet coil at DC":"3.3 W","Holding power of magnet coil at DC":"3.3 W","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"screw-type terminals","at ambient temperature 40 °C rated value":"22 A","Type of voltage of the control supply voltage":"DC","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=317992&mlfb=3RT1017-1BD41","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1017-1BD41/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional alternative to 3RT1017-1BD41?","answer":"The 3RT1016-1AG61 is a size S00 contactor from the same SIRIUS family but with a 24 VAC coil instead of 24 VDC. The mechanical footprint and terminal layout are identical, so it drops into the same panel without rewiring the power circuit, but the coil supply must be changed from DC to AC."},{"question":"Where can I buy 3RT1017-1BD41 and get current pricing?","answer":"This part is sourced and quoted to order against an RFQ through our independent distribution channel. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer."},{"question":"What wire sizes does the screw terminal accept?","answer":"The main circuit screw terminals accept 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), and up to 2x (0.75 to 4 mm²) solid or stranded. AWG equivalents are 2x (20 to 16), 2x (18 to 14), and 1x 12."},{"question":"What compliance documentation is available for 3RT1017-1BD41?","answer":"As a standard Siemens SIRIUS catalog product, this contactor carries CE marking for the European market and is designed to meet IEC/EN 60947-4-1. RoHS and REACH compliance declarations are available from Siemens on request. The reference code per DIN EN 81346-2 is Q."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1017-1BD41","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1017-1BD41 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}