{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1017-1WB41","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1017-1WB41","canonicalUrl":"https://aoctrl.com/siemens/3RT1017-1WB41","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1017-1WB41","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S00, 24 VDC coil, screw-type terminals, IP20, for 35 mm DIN rail.","salesMarkdown":"The 24 VDC coil draws 1.4 W holding power, with a pick-up threshold of 0.85 x rated voltage and a drop-out threshold of 1.85 x rated voltage. Rated operational current at AC-12 (resistive load) is 10 A at 24 V. For inductive motor loads, the contactor is rated for 5.5 kW at 400 V AC-3 duty and 8.5 A at 400 V AC-4 duty. The built-in varistor surge suppressor handles coil suppression internally. Width is 45 mm, height 57.5 mm, depth 72 mm. IP20 finger-safe protection on the front and terminals. Screw-type terminals for the main current circuit accept 2x (0.5...1.5 mm²), 2x (0.75...2.5 mm²), or max. 2x (0.75...4 mm²) solid/stranded conductors; AWG equivalents are 2x (20...16), 2x (18...14), 1x 12. ## Short-Circuit Coordination and Ratings Pollution degree 3 (industrial environment).","metaTitle":"Siemens 3RT1017-1WB41 SIRIUS Power Contactor, 24 VDC Coil, S","metaDescription":"Siemens 3RT1017-1WB41 SIRIUS power contactor, size S00, 24 VDC coil, screw terminals, IP20. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"72 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"57.5 mm","Maximum":"2 000 m","At The Side":"6 mm","Rated Value":"24 V","On The Front":"IP20","Initial Value":"0.85","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Full-scale value":"1.85","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 500 V rated value":"5.5 kW","at 690 V rated value":"5.5 kW","Instantaneous Contact":"1","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)","at AC-2 at 400 V rated value":"5.5 kW","at AC-4 at 400 V rated value":"8.5 A","Design of the surge suppressor":"with varistor","Closing power of magnet coil at DC":"1.4 W","Holding power of magnet coil at DC":"1.4 W","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"screw-type terminals","at ambient temperature 40 °C rated value":"22 A","Type of voltage of the control supply voltage":"DC","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=398170&mlfb=3RT1017-1WB41","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1017-1WB41/alternatives.json"},"ai":{"faq":[{"question":"What is the coil voltage and power consumption for 3RT1017-1WB41?","answer":"The coil is rated 24 VDC. Closing and holding power are both 1.4 W. Pick-up threshold is 0.85 x rated voltage; drop-out threshold is 1.85 x rated voltage."},{"question":"What are the motor ratings for 3RT1017-1WB41 at 400 V?","answer":"At 400 V AC-3 duty, the contactor is rated for 5.5 kW motor load. At 400 V AC-4 duty (frequent starting/plugging), the rated operational current is 8.5 A."},{"question":"What short-circuit protection does 3RT1017-1WB41 require?","answer":"For Type 2 coordination (no damage), use a gL/gG 20 A fuse upstream. For Type 1 coordination (contactor may need replacement), use a gL/gG 35 A fuse."},{"question":"Where can I buy 3RT1017-1WB41 and how is it quoted?","answer":"The 3RT1017-1WB41 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at the time of quote submission."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1017-1WB41","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1017-1WB41 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}