{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1017-2AF01","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1017-2AF01","canonicalUrl":"https://aoctrl.com/siemens/3RT1017-2AF01","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1017-2AF01","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS S00 power contactor, 3RT1017-2AF01, 5.5 kW at 400 V AC-2, 8.5 A AC-4, spring-loaded terminals, 45 mm width.","salesMarkdown":"For more demanding AC-4 duty — plugging, inching, or reversing a squirrel-cage motor at full stall current — the contactor is rated 8.5 A at 400 V. At higher line voltages the contactor delivers 5.5 kW at both 500 V and 690 V, which covers 480 V and 600 V class systems common in North American and some export panels. For DC switching — solenoid or brake loads — the contactor handles 10 A at 24 V, 2 A at 60 V, 1 A at 110 V, and 0.3 A at 220 V. Main circuit terminals are spring-loaded (cage-clamp type), accepting 2x (0.25 to 2.5 mm²) solid or stranded, or 2x (24 to 14 AWG). No screw torque to verify — strip to 8 mm and push in. That 20 A Type 2 limit is the one to spec if you want to avoid replacing the contactor after a downstream fault. Mechanical service life is 30 million operating cycles, which for a contactor that cycles once per minute translates to roughly 57 years — not the limiting factor in most panels.","metaTitle":"Siemens 3RT1017-2AF01 SIRIUS S00 Power Contactor, 5.5 kW at","metaDescription":"Siemens 3RT1017-2AF01 SIRIUS S00 power contactor. 5.5 kW at 400 V AC-2, 8.5 A AC-4. Spring-loaded terminals, 45 mm wide, IP20. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"73 mm","Solid":"2x (0.25 ... 2.5 mm²)","Width":"45 mm","Height":"60 mm","Maximum":"2 000 m","at 50 Hz":"0.8 ... 1.1","at 60 Hz":"0.85 ... 1.1","At The Side":"6 mm","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"110 V","at 500 V rated value":"5.5 kW","at 60 Hz rated value":"110 V","at 690 V rated value":"5.5 kW","Instantaneous Contact":"1","Side-by-side mounting":"Yes","For Main Current Circuit":"spring-loaded terminals","Single Or Multi-Stranded":"2x (0,25 ... 2,5 mm²)","at AC-2 at 400 V rated value":"5.5 kW","at AC-4 at 400 V rated value":"8.5 A","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (24 ... 14)","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.25 ... 1.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (24 ... 14)","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"spring-loaded terminals","at ambient temperature 40 °C rated value":"22 A","Apparent holding power of magnet coil at AC":"4.4 V·A","Apparent pick-up power of magnet coil at AC":"27 V·A","Finely Stranded Without Core End Processing":"2x (0.25 ... 2.5 mm²)","Type of voltage of the control supply voltage":"AC","Inductive power factor with closing power of the coil":"0.8","Inductive power factor with the holding power of the coil":"0.27","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=330913&mlfb=3RT1017-2AF01","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1017-2AF01/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional alternative — 3RT1016-2AP02?","answer":"The 3RT1016-2AP02 is a peer in the same S00 frame size, but it uses screw terminals instead of spring-loaded terminals. The 3RT1017-2AF01 has cage-clamp main terminals; the 3RT1016-2AP02 has screw-type. Panel wiring must be adapted if switching from one to the other. Motor ratings and dimensions are otherwise similar within the S00 family."},{"question":"What is the depth of 3RT1017-2AF01?","answer":"73 mm. Combined with a width of 45 mm and height of 60 mm, it fits the S00 frame footprint."},{"question":"What conductor sizes do the spring-loaded terminals accept?","answer":"Solid and stranded: 2x (0.25 to 2.5 mm²) or 2x (24 to 14 AWG)."},{"question":"Will 3RT1017-2AF01 drop into a panel specified around 3RT1016-2AP02 without rewiring?","answer":"Mechanically yes — same S00 frame, same DIN-rail mounting, same 45 mm width. But the 3RT1016-2AP02 uses screw terminals; this part uses spring-loaded terminals. If the panel was wired with ferruled conductors for screw clamps, those same conductors will insert into the cage clamps, but the wiring method changes from screw-torque to push-in. No rewiring of the circuit is needed, but the termination technique differs."},{"question":"What compliance documentation is available for 3RT1017-2AF01?","answer":"The evidence does not list specific compliance certificates (RoHS, REACH, UL, IEC) for this order code. Standard Siemens SIRIUS contactors carry CE marking for the European market and UL/CSA listings for North America when ordered with the appropriate suffix. The IP20 front and terminal ratings and pollution degree 3 are declared per IEC 60947-4-1. For a specific certificate request, include the requirement in your RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1017-2AF01","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1017-2AF01 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}