{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1017-2AG61","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1017-2AG61","canonicalUrl":"https://aoctrl.com/siemens/3RT1017-2AG61","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1017-2AG61","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, 3RT1017-2AG61, size S00, 5.5 kW at 500 V AC-3, spring-loaded terminals, 24 VDC coil, screw and snap-on mounting.","salesMarkdown":"The main contacts are spring-loaded terminals, accepting 2x (0.25 to 2.5 mm²) solid or stranded wire, or 2x (24 to 14 AWG). This means no screw torque to verify — the wire pushes in and the cage clamps it. Rated for AC-3 duty at 5.5 kW at both 500 V and 690 V — this is the motor-switching rating that governs most pump, fan, and conveyor applications. AC-2 at 400 V also carries 5.5 kW, for slip-ring motor starting. For resistive loads (AC-12), the maximum operating current is 10 A. The coil operates at 50/60 Hz with a voltage tolerance of 0.85 to 1.1 times rated, so a 24 VDC coil holds reliably from about 20.4 V to 26.4 V. Mechanical life is 30 million cycles typical, meaning this contactor outlasts most equipment refreshes in a standard switching schedule. ## Integration and mounting details Dimensions: 45 mm wide, 60 mm high, 73 mm deep. Side-by-side mounting is permitted with no derating gap — you can pack S00 contactors tight on the rail. The front face carries IP20 finger protection; the terminals are also IP20, so the panel interior is touch-safe without additional shrouds. For short-circuit coordination, Type 1 requires a 35 A gL/gG fuse; Type 2 requires a 20 A gL/gG fuse — this matters for selectivity studies on the panel's feeder breaker.","metaTitle":"Siemens 3RT1017-2AG61 SIRIUS Power Contactor, S00, 5.5 kW at","metaDescription":"Siemens 3RT1017-2AG61 SIRIUS power contactor, size S00, 5.5 kW at 500 V AC-3, spring-loaded terminals, 24 VDC coil. Current production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"73 mm","Solid":"2x (0.25 ... 2.5 mm²)","Width":"45 mm","Height":"60 mm","Maximum":"2 000 m","at 50 Hz":"0.85 ... 1.1","at 60 Hz":"0.85 ... 1.1","At The Side":"6 mm","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"100 V","at 500 V rated value":"5.5 kW","at 60 Hz rated value":"100 ... 110 V","at 690 V rated value":"5.5 kW","Instantaneous Contact":"1","Side-by-side mounting":"Yes","For Main Current Circuit":"spring-loaded terminals","Single Or Multi-Stranded":"2x (0,25 ... 2,5 mm²)","at AC-2 at 400 V rated value":"5.5 kW","at AC-4 at 400 V rated value":"8.5 A","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (24 ... 14)","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.25 ... 1.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (24 ... 14)","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"spring-loaded terminals","at ambient temperature 40 °C rated value":"22 A","Apparent holding power of magnet coil at AC":"5.1 V·A","Apparent pick-up power of magnet coil at AC":"31.7 V·A","Finely Stranded Without Core End Processing":"2x (0.25 ... 2.5 mm²)","Type of voltage of the control supply voltage":"AC","Inductive power factor with closing power of the coil":"0.77","Inductive power factor with the holding power of the coil":"0.27","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=15796&mlfb=3RT1017-2AG61","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1017-2AG61/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this contactor?","answer":"AC-3 motor power is 5.5 kW at 500 V and 5.5 kW at 690 V. The coil is 24 VDC, drawing 10 A. Mechanical life is 30 million cycles. Dimensions are 45 mm wide, 60 mm high, 73 mm deep."},{"question":"Will this drop into a panel built for the 3RT1017-1AP01?","answer":"Both are S00 frame size with the same 45 mm width and DIN-rail mounting, so the physical footprint is identical. The 3RT1017-2AG61 uses spring-loaded terminals, while the 1AP01 variant may use screw terminals — verify the wiring method matches your panel's termination style."},{"question":"What compliance documentation is available?","answer":"The contactor carries IP20 front and terminal protection, pollution degree 3 rating, and is designed to IEC/EN standards. Specific RoHS, REACH, UL, and IEC declarations are available from the manufacturer's documentation portal for this order code."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1017-2AG61","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1017-2AG61 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}