{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1017-2AN62","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1017-2AN62","canonicalUrl":"https://aoctrl.com/siemens/3RT1017-2AN62","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1017-2AN62","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, Size S00, 3RT1017-2AN62, spring-loaded terminals, 45 mm width, AC-3 5.5 kW at 400 V.","salesMarkdown":"The Siemens 3RT1017-2AN62 is a SIRIUS power contactor in the compact Size S00 frame — 45 mm wide, 60 mm tall, 73 mm deep — designed for screw and snap-on mounting onto 35 mm DIN rail per DIN EN 50022. Spring-loaded terminals on the main circuit accept 2x (0.25 to 2.5 mm²) solid or stranded wire, which saves panel-builder time versus screw-clamp variants. It's rated for AC-3 motor duty at 5.5 kW on 400 V, and carries an AC-4 switching current of 8.5 A at the same voltage for reversing or inching applications. If you're doing plugging or jogging (AC-4 duty), the contactor is rated at 8.5 A at 400 V, which is roughly 4 kW on a typical 400 V motor. The auxiliary contact block carries 10 A at AC-12 (control-circuit resistive loads), and the DC switching capability covers 24 V at 10 A, 60 V at 2 A, 110 V at 1 A, and 220 V at 0.3 A — enough for most PLC output interface circuits. For fuse coordination, Type 2 (no damage to the contactor) requires a 20 A gL/gG fuse; The screw and snap-on mounting mechanism lets you install or remove it without tools — useful during panel rework or when swapping a failed unit. Strip length for the spring terminals is 8 mm; use ferruled stranded wire for reliable contact.","metaTitle":"Siemens 3RT1017-2AN62 SIRIUS Power Contactor, Size S00, 45 m","metaDescription":"Siemens 3RT1017-2AN62 SIRIUS power contactor, Size S00, 45 mm wide, spring-loaded terminals, AC-3 5.5 kW at 400 V. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"73 mm","Solid":"2x (0.25 ... 2.5 mm²)","Width":"45 mm","Height":"60 mm","Maximum":"2 000 m","at 50 Hz":"0.85 ... 1.1","at 60 Hz":"0.85 ... 1.1","At The Side":"6 mm","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"200 V","at 500 V rated value":"5.5 kW","at 60 Hz rated value":"200 ... 220 V","at 690 V rated value":"5.5 kW","Instantaneous Contact":"0","Side-by-side mounting":"Yes","For Main Current Circuit":"spring-loaded terminals","Single Or Multi-Stranded":"2x (0,25 ... 2,5 mm²)","at AC-2 at 400 V rated value":"5.5 kW","at AC-4 at 400 V rated value":"8.5 A","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (24 ... 14)","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.25 ... 1.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (24 ... 14)","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"spring-loaded terminals","at ambient temperature 40 °C rated value":"22 A","Apparent holding power of magnet coil at AC":"5.1 V·A","Apparent pick-up power of magnet coil at AC":"31.7 V·A","Finely Stranded Without Core End Processing":"2x (0.25 ... 2.5 mm²)","Type of voltage of the control supply voltage":"AC","Inductive power factor with closing power of the coil":"0.77","Inductive power factor with the holding power of the coil":"0.27","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=439629&mlfb=3RT1017-2AN62","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1017-2AN62/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RT1017-2AN62 and how do I get a price?","answer":"We source this contactor through independent distribution channels. Submit an RFQ for current pricing and availability — confirmed at quote time."},{"question":"When sourcing 3RT1017-2AN62, what's the closest functional second-source — 3RT1016-2AP02?","answer":"The 3RT1016-2AP02 is a smaller Size S00 contactor (same frame) but with screw-type terminals instead of spring-loaded. It shares the same AC-3 rating of 5.5 kW at 400 V and the same mounting footprint, so it drops into the same panel without rewiring if the terminal type is acceptable."},{"question":"What is 3RT1017-2AN62's listed depth (73 mm) on this component line?","answer":"The depth is 73 mm, with a width of 45 mm and height of 60 mm — compact for a Size S00 contactor."},{"question":"What is 3RT1017-2AN62's listed solid (2x (0.25... 2.5 mm²)) on this component line?","answer":"The spring-loaded terminals accept 2x (0.25 to 2.5 mm²) solid or stranded wire, or 2x (24 to 14 AWG)."},{"question":"Will 3RT1017-2AN62 drop into a panel that was specified around 3RT1016-2AP02 without rewiring?","answer":"Yes — both are Size S00 with the same 45 mm width and DIN-rail mounting. The only difference is terminal type: spring-loaded on the 3RT1017-2AN62 versus screw-type on the 3RT1016-2AP02. No rewiring of the panel layout is needed."},{"question":"What compliance documentation does this brand provide for 3RT1017-2AN62 (RoHS, REACH, UL, IEC)?","answer":"As a Siemens SIRIUS product, it carries CE marking and is designed to IEC/EN 60947-4-1. UL and CSA listings are standard for the series. RoHS and REACH declarations are available from Siemens documentation."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1017-2AN62","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1017-2AN62 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}