{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1017-2AR62","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1017-2AR62","canonicalUrl":"https://aoctrl.com/siemens/3RT1017-2AR62","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1017-2AR62","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT1017-2AR62 power contactor, size S00, 400 V at 50 Hz, spring-loaded terminals, screw and snap-on mounting.","salesMarkdown":"Rated for 400 V at 50 Hz, it carries motor ratings of 5.5 kW at both 500 V and 690 V under AC-2 duty, and 8.5 A at 400 V under AC-4 duty — the AC-4 figure governs the reversing or inching cycles where the contactor makes and breaks the motor current under load. For resistive loads (AC-12), the maximum operating current is 10 A. The main current circuit uses spring-loaded terminals, accepting 2x (0.25 to 2.5 mm²) solid or stranded wire, or 2x (24 to 14 AWG). This means no screw-torque check during commissioning — just strip to 8 mm and push in. Side-by-side mounting is permitted, with only 6 mm clearance needed at the side, which lets you pack multiple contactors in a row without wasting panel width. That makes it suitable for industrial environments like machine tools, conveyor lines, and pump stations where the panel isn't climate-controlled. The auxiliary contact ratings cover the common control voltages: 10 A at 24 V, 6 A at 230 V, 3 A at 400 V, and 0.3 A at 220 V DC. The 24 V rating is the one most often used for PLC outputs — it handles the inrush of multiple contactor coils downstream. These are the fuse ratings to put on your BOM if you're designing the motor branch circuit. Electrical life will be lower and depends on the switching category and current, but 30 million cycles means the mechanism outlasts most panel rebuild cycles.","metaTitle":"Siemens 3RT1017-2AR62 SIRIUS Power Contactor, S00, 400V 50Hz","metaDescription":"Siemens SIRIUS 3RT1017-2AR62 power contactor, size S00, rated 400V at 50Hz. Spring-loaded terminals, DIN rail mount. Current lifecycle stage. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"73 mm","Solid":"2x (0.25 ... 2.5 mm²)","Width":"45 mm","Height":"60 mm","Maximum":"2 000 m","at 50 Hz":"0.85 ... 1.1","at 60 Hz":"0.85 ... 1.1","At The Side":"6 mm","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"400 V","at 500 V rated value":"5.5 kW","at 60 Hz rated value":"400 ... 440 V","at 690 V rated value":"5.5 kW","Instantaneous Contact":"0","Side-by-side mounting":"Yes","For Main Current Circuit":"spring-loaded terminals","Single Or Multi-Stranded":"2x (0,25 ... 2,5 mm²)","at AC-2 at 400 V rated value":"5.5 kW","at AC-4 at 400 V rated value":"8.5 A","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (24 ... 14)","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.25 ... 1.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (24 ... 14)","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"spring-loaded terminals","at ambient temperature 40 °C rated value":"22 A","Apparent holding power of magnet coil at AC":"5.1 V·A","Apparent pick-up power of magnet coil at AC":"31.7 V·A","Finely Stranded Without Core End Processing":"2x (0.25 ... 2.5 mm²)","Type of voltage of the control supply voltage":"AC","Inductive power factor with closing power of the coil":"0.77","Inductive power factor with the holding power of the coil":"0.27","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=467876&mlfb=3RT1017-2AR62","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1017-2AR62/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional second-source to 3RT1017-2AR62?","answer":"The closest peer in the same SIRIUS S00 family is 3RT1016-2AP02, which shares the same frame size and mounting footprint. The key difference is the coil voltage — 3RT1017-2AR62 is a 400 V 50 Hz coil, while 3RT1016-2AP02 uses a different control voltage. Verify the coil rating before substituting."},{"question":"What is the depth of 3RT1017-2AR62?","answer":"The depth is 73 mm. Combined with the 45 mm width and 60 mm height, it fits the S00 frame envelope."},{"question":"What wire sizes does the spring-loaded terminal accept?","answer":"The main circuit terminals accept 2x (0.25 to 2.5 mm²) solid or stranded wire, or 2x (24 to 14 AWG). No screw torque is needed — strip to 8 mm and push in."},{"question":"Will 3RT1017-2AR62 drop into a panel specified for 3RT1016-2AP02?","answer":"Mechanically yes — both are S00 frame size with the same DIN-rail mounting and 45 mm width. Electrically, check the coil voltage: 3RT1017-2AR62 is a 400 V 50 Hz coil. If the panel was wired for a different coil voltage, the contactor won't pull in."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1017-2AR62","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1017-2AR62 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}