{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1017-2HB41","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1017-2HB41","canonicalUrl":"https://aoctrl.com/siemens/3RT1017-2HB41","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1017-2HB41","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, 3RT1017-2HB41, size S00, 24 V DC coil, 5.5 kW at 400 V AC-2, spring-loaded terminals, IP20, screw and snap-on 35 mm DIN rail.","salesMarkdown":"## SIRIUS S00 power contactor, 24 V DC coil — what fits and what doesn't Its 24 V DC coil draws 2.3 W to close and holds at the same 2.3 W — a steady-state power figure that matters for DC supply sizing and heat buildup inside a sealed enclosure. The spring-loaded terminals on the main circuit accept 2x (0.25 to 2.5 mm²) solid or stranded wire — no screwdriver needed for terminations, which speeds up panel wiring and reduces torque-verification steps. ## Coil and auxiliary contact ratings The 24 V DC coil has a closing power and holding power both rated at 2.3 W. That flat power curve simplifies the DC supply budget — no inrush spike to design around. One instantaneous auxiliary contact is built in (NO/NC configuration not specified in the base data).","metaTitle":"Siemens 3RT1017-2HB41 SIRIUS Power Contactor, 24 V DC, S00","metaDescription":"Siemens 3RT1017-2HB41 SIRIUS power contactor, size S00, 24 V DC coil, 5.5 kW at 400 V AC-2, spring-loaded terminals, IP20. Current lifecycle. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"73 mm","Solid":"2x (0.25 ... 2.5 mm²)","Width":"45 mm","Height":"60 mm","Maximum":"2 000 m","At The Side":"6 mm","Rated Value":"24 V","On The Front":"IP20","Initial Value":"0.7","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP20","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Full-scale value":"1.25","Size of contactor":"S00","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"30 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 500 V rated value":"5.5 kW","at 690 V rated value":"5.5 kW","Instantaneous Contact":"1","Side-by-side mounting":"Yes","For Main Current Circuit":"spring-loaded terminals","Single Or Multi-Stranded":"2x (0,25 ... 2,5 mm²)","at AC-2 at 400 V rated value":"5.5 kW","at AC-4 at 400 V rated value":"8.5 A","Closing power of magnet coil at DC":"2.3 W","Holding power of magnet coil at DC":"2.3 W","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 20 A","at AWG conductors for main contacts":"2x (24 ... 14)","With Type Of Coordination 1 Required":"fuse gL/gG: 35 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.25 ... 1.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (24 ... 14)","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"spring-loaded terminals","at ambient temperature 40 °C rated value":"22 A","Finely Stranded Without Core End Processing":"2x (0.25 ... 2.5 mm²)","Type of voltage of the control supply voltage":"DC","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=145300&mlfb=3RT1017-2HB41","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1017-2HB41/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RT1017-2HB41 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ to confirm current availability and pricing at quote time."},{"question":"What is 3RT1017-2HB41's listed depth?","answer":"The depth is 73 mm, which fits standard S00 contactor depth profiles for DIN-rail enclosures."},{"question":"What wire sizes do the spring-loaded terminals accept?","answer":"The main circuit spring-loaded terminals accept 2x (0.25 to 2.5 mm²) solid or stranded conductors, or 2x (24 to 14 AWG)."},{"question":"What is the AC-2 motor rating at 400 V?","answer":"Rated 5.5 kW at 400 V for AC-2 duty — suited for wound-rotor motor switching in moderate-duty applications."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1017-2HB41","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1017-2HB41 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}