{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1023-3AF00","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1023-3AF00","canonicalUrl":"https://aoctrl.com/siemens/3RT1023-3AF00","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1023-3AF00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S0, 3 NO main contacts, 24 VDC coil, 45 mm width, screw terminals, IP20 front, current production.","salesMarkdown":"For straight AC-3 motor starting, the power ratings are 4.5 kW at 500 V and 5.5 kW at 690 V. Main circuit terminals accept screw-type connections: solid or stranded 2x (0.25 to 2.5 mm²) or 2x (2.5 to 6 mm²), with a maximum of 2x 10 mm². For AWG, that's 2x (16 to 12) or 2x (14 to 10), or 1x 8. Short-circuit coordination: type 2 requires a gL/gG fuse rated 25 A; type 1 allows up to 63 A. Side-by-side mounting is allowed with a 6 mm gap at the side, so you can pack them tight on the rail without derating.","metaTitle":"Siemens 3RT1023-3AF00 SIRIUS Power Contactor, 3 NO, 24 VDC C","metaDescription":"Siemens 3RT1023-3AF00 SIRIUS power contactor, size S0, 3 NO main contacts, 24 VDC coil, 45 mm wide, screw terminals, IP20 front. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"90 mm","Solid":"2x (0.25 ... 2.5 mm²)","Width":"45 mm","Height":"85 mm","Maximum":"2 000 m","at 50 Hz":"0.8 ... 1.1","At The Side":"6 mm","On The Front":"IP20","1 Rated Value":"50 Hz","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP00","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Size of contactor":"S0","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"110 V","at 500 V rated value":"4.5 kW","at 690 V rated value":"5.5 kW","Instantaneous Contact":"0","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (1 ... 2,5 mm²), 2x (2,5 ... 6 mm²), max. 2x 10 mm²","at AC-2 at 400 V rated value":"4 kW","at AC-4 at 400 V rated value":"8.5 A","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 25 A","at AWG conductors for main contacts":"2x (16 ... 12), 2x (14 ... 10), 1x 8","With Type Of Coordination 1 Required":"fuse gL/gG: 63 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.25 ... 1.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (24 ... 14)","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"spring-loaded terminals","at ambient temperature 40 °C rated value":"40 A","Apparent holding power of magnet coil at AC":"7.8 V·A","Apparent pick-up power of magnet coil at AC":"61 V·A","Finely Stranded Without Core End Processing":"2x (0.25 ... 2.5 mm²)","Type of voltage of the control supply voltage":"AC","Inductive power factor with closing power of the coil":"0.82","Inductive power factor with the holding power of the coil":"0.24","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=347434&mlfb=3RT1023-3AF00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1023-3AF00/alternatives.json"},"ai":{"faq":[{"question":"What is the depth of 3RT1023-3AF00?","answer":"The depth is 90 mm."},{"question":"What wire sizes does the 3RT1023-3AF00 accept on the main terminals?","answer":"Screw terminals accept solid or stranded 2x (0.25 to 2.5 mm²), 2x (2.5 to 6 mm²), or max 2x 10 mm². AWG equivalents are 2x (16 to 12), 2x (14 to 10), or 1x 8."},{"question":"Will 3RT1023-3AF00 drop into a panel specified for 3RT1023-1AL20 without rewiring?","answer":"Both are size S0 contactors on the same 45 mm footprint with screw terminals and 35 mm DIN rail mounting. The main difference is the coil voltage: 3RT1023-3AF00 uses 24 VDC, while the 1AL20 variant uses a different coil. If the panel wiring and control voltage match 24 VDC, the swap is mechanical and electrical drop-in."},{"question":"Where can I buy 3RT1023-3AF00?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1023-3AF00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1023-3AF00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}