{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1024-1AV00","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1024-1AV00","canonicalUrl":"https://aoctrl.com/siemens/3RT1024-1AV00","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1024-1AV00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, 3RT1024-1AV00, S0 frame, 3-pole NO, 7.5 kW at 500 V / 690 V, AC-4 12.5 A, screw terminals, 45 mm width, DIN rail mount.","salesMarkdown":"## SIRIUS S0 Power Contactor — 3RT1024-1AV00 It is designed for switching three-phase motor loads up to 7.5 kW at 500 V or 690 V, 50 Hz, per the datasheet ratings. The 45 mm width (3TE) occupies one slot in a typical panel layout. The contactor is rated for AC-4 duty at 12.5 A at 400 V, which governs switching of motor loads under inrush or plugging conditions — the more demanding duty cycle compared to AC-3. For type 2 coordination (no-weld), a 25 A gL/gG fuse is specified; type 1 coordination allows a 63 A fuse. Main circuit terminals accept solid or stranded conductors: 2x (0.5–1.5 mm²), 2x (0.75–2.5 mm²), or max 2x (0.75–4 mm²) for the control circuit; for the main contacts, 2x (1–2.5 mm²), 2x (2.5–6 mm²), or max 2x 10 mm². AWG equivalents are 2x (16–12), 2x (14–10), and 1x 8. The front of the contactor carries an IP20 rating (finger-safe), while the terminal area is rated IP00 — meaning the connection points require additional protection in the enclosure to prevent accidental contact. ## Environmental and Installation Conditions Pollution degree 3 is specified.","metaTitle":"Siemens 3RT1024-1AV00 SIRIUS Power Contactor, 7.5 kW","metaDescription":"Siemens 3RT1024-1AV00 SIRIUS power contactor, S0 frame, 3 NO main contacts, 7.5 kW at 500/690 V, AC-4 rated 12.5 A. Active production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"91 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"85 mm","Maximum":"2 000 m","at 50 Hz":"0.8 ... 1.1","At The Side":"6 mm","On The Front":"IP20","1 Rated Value":"50 Hz","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP00","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Size of contactor":"S0","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"400 V","at 500 V rated value":"7.5 kW","at 690 V rated value":"7.5 kW","Instantaneous Contact":"0","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (1 ... 2,5 mm²), 2x (2,5 ... 6 mm²), max. 2x 10 mm²","at AC-2 at 400 V rated value":"5.5 kW","at AC-4 at 400 V rated value":"12.5 A","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 25 A","at AWG conductors for main contacts":"2x (16 ... 12), 2x (14 ... 10), 1x 8","With Type Of Coordination 1 Required":"fuse gL/gG: 63 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"screw-type terminals","at ambient temperature 40 °C rated value":"40 A","Apparent holding power of magnet coil at AC":"7.8 V·A","Apparent pick-up power of magnet coil at AC":"61 V·A","Type of voltage of the control supply voltage":"AC","Inductive power factor with closing power of the coil":"0.82","Inductive power factor with the holding power of the coil":"0.24","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=472618&mlfb=3RT1024-1AV00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1024-1AV00/alternatives.json"},"ai":{"faq":[{"question":"What is the depth of 3RT1024-1AV00?","answer":"The depth is 91 mm, with a width of 45 mm and height of 85 mm, per the dimensional specifications."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1024-1AV00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1024-1AV00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}