{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1024-3AN60","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1024-3AN60","canonicalUrl":"https://aoctrl.com/siemens/3RT1024-3AN60","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1024-3AN60","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, S0 frame, 24 VDC coil, screw terminals, 7.5 kW at 400 V AC-3, 45 mm width, IP20 front.","salesMarkdown":"## Integrator note The Siemens 3RT1024-3AN60 is a SIRIUS power contactor in the S0 frame, rated for 7.5 kW motor switching at 400 V in AC-3 duty. The 24 VDC coil pulls in at nominal and holds to the dropout threshold — verify your control supply stays above the minimum dropout voltage under load. Front face is IP20 — safe for open-panel wiring; terminal area is IP00, so keep live parts behind a gland plate or enclosure door. Type 1 coordination allows a 63 A gL/gG fuse — the contactor may need replacement after a fault but the circuit clears.","metaTitle":"Siemens 3RT1024-3AN60 SIRIUS Power Contactor, S0, 24 VDC, 7.","metaDescription":"Siemens 3RT1024-3AN60 SIRIUS power contactor, S0 frame, 24 VDC coil, 7.5 kW at 400 V AC-3. Current lifecycle stage. Available to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"90 mm","Solid":"2x (0.25 ... 2.5 mm²)","Width":"45 mm","Height":"85 mm","Maximum":"2 000 m","at 50 Hz":"0.8 ... 1.1","at 60 Hz":"0.85 ... 1.1","At The Side":"6 mm","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP00","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Size of contactor":"S0","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"200 V","at 500 V rated value":"7.5 kW","at 60 Hz rated value":"200 ... 220 V","at 690 V rated value":"7.5 kW","Instantaneous Contact":"0","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (1 ... 2,5 mm²), 2x (2,5 ... 6 mm²), max. 2x 10 mm²","at AC-2 at 400 V rated value":"5.5 kW","at AC-4 at 400 V rated value":"12.5 A","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 25 A","at AWG conductors for main contacts":"2x (16 ... 12), 2x (14 ... 10), 1x 8","With Type Of Coordination 1 Required":"fuse gL/gG: 63 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.25 ... 1.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (24 ... 14)","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"spring-loaded terminals","at ambient temperature 40 °C rated value":"40 A","Apparent holding power of magnet coil at AC":"7.5 V·A","Apparent pick-up power of magnet coil at AC":"69 V·A","Finely Stranded Without Core End Processing":"2x (0.25 ... 2.5 mm²)","Type of voltage of the control supply voltage":"AC","Inductive power factor with closing power of the coil":"0.76","Inductive power factor with the holding power of the coil":"0.28","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=231717&mlfb=3RT1024-3AN60","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1024-3AN60/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional second-source for 3RT1024-3AN60?","answer":"The 3RT1023-1AL20 is a smaller S00-frame contactor; it drops into the same DIN rail footprint but has lower motor ratings and a different coil voltage. Verify your load current and coil supply before substituting."},{"question":"Will 3RT1024-3AN60 drop into a panel designed for 3RT1023-1AL20?","answer":"The 3RT1024-3AN60 is 45 mm wide versus the S00 frame's 45 mm width — same DIN rail pitch, but the S0 frame is taller (85 mm vs S00's 58 mm). Check enclosure depth clearance as well (90 mm vs S00's 73 mm). Rewiring terminals is identical: both use screw-type."},{"question":"What compliance documentation is available for 3RT1024-3AN60?","answer":"Siemens SIRIUS contactors carry CE marking, UL/CSA listings, and RoHS/REACH declarations. Specific certificates are available on request."},{"question":"Where can I buy 3RT1024-3AN60?","answer":"This part is sourced and quoted to order against an RFQ through independent industrial distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1024-3AN60","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1024-3AN60 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}