{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1024-3AP60","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1024-3AP60","canonicalUrl":"https://aoctrl.com/siemens/3RT1024-3AP60","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1024-3AP60","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT1024-3AP60, Size S0 power contactor, 45 mm wide, screw-type terminals, 7.5 kW at 690 V AC-3, 50/60 Hz.","salesMarkdown":"The contactor is rated for AC-3 duty at 7.5 kW on both 500 V and 690 V supplies, at either 50 Hz or 60 Hz. For the commissioning engineer, the AC-4 rating of 12.5 A at 400 V defines the inching or plugging capability — the current it can break during high-stress reversing or jogging cycles, not just steady-state running. The 45 mm width and 85 mm height fit standard S0 panel layouts. Screw-type terminals on the main circuit accept 2x (0.25 to 2.5 mm²) solid or 2x (1 to 2.5 mm²) stranded, with a maximum of 2x 10 mm² or 1x 8 AWG. For the wireman, that means no ferrule crimping is required for the smaller conductors, but the larger 10 mm² termination needs careful torque control. ## Environmental and operating limits For the field service tech, the coil operates on a 0.8 to 1.1 times the rated voltage at both 50 Hz and 60 Hz, ensuring pickup across typical line fluctuations.","metaTitle":"Siemens 3RT1024-3AP60 SIRIUS Power Contactor, Size S0, 7.5 k","metaDescription":"Siemens SIRIUS 3RT1024-3AP60 power contactor, Size S0, 45 mm wide, screw terminals, 7.5 kW at 690 V AC-3. Current lifecycle stage. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"90 mm","Solid":"2x (0.25 ... 2.5 mm²)","Width":"45 mm","Height":"85 mm","Maximum":"2 000 m","at 50 Hz":"0.8 ... 1.1","at 60 Hz":"0.8 ... 1.1","At The Side":"6 mm","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP00","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Size of contactor":"S0","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"220 V","at 500 V rated value":"7.5 kW","at 60 Hz rated value":"240 V","at 690 V rated value":"7.5 kW","Instantaneous Contact":"0","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (1 ... 2,5 mm²), 2x (2,5 ... 6 mm²), max. 2x 10 mm²","at AC-2 at 400 V rated value":"5.5 kW","at AC-4 at 400 V rated value":"12.5 A","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 25 A","at AWG conductors for main contacts":"2x (16 ... 12), 2x (14 ... 10), 1x 8","With Type Of Coordination 1 Required":"fuse gL/gG: 63 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.25 ... 1.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (24 ... 14)","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"spring-loaded terminals","at ambient temperature 40 °C rated value":"40 A","Apparent holding power of magnet coil at AC":"7.5 V·A","Apparent pick-up power of magnet coil at AC":"69 V·A","Finely Stranded Without Core End Processing":"2x (0.25 ... 2.5 mm²)","Type of voltage of the control supply voltage":"AC","Inductive power factor with closing power of the coil":"0.76","Inductive power factor with the holding power of the coil":"0.28","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=144303&mlfb=3RT1024-3AP60","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1024-3AP60/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this contactor?","answer":"The contactor is rated for 7.5 kW at both 500 V and 690 V AC-3 duty, with an AC-4 breaking current of 12.5 A at 400 V. It operates at 50 Hz or 60 Hz with a coil pickup range of 0.8 to 1.1 times rated voltage."},{"question":"What are the physical dimensions and mounting requirements?","answer":"The contactor measures 45 mm wide, 85 mm high, and 90 mm deep. It mounts on a 35 mm DIN rail per EN 50022 via screw or snap-on, with a 6 mm side clearance required for heat dissipation."},{"question":"What wire sizes does the screw terminal accept?","answer":"The main circuit screw terminals accept 2x (0.25 to 2.5 mm²) solid or 2x (1 to 2.5 mm²) stranded, with a maximum of 2x 10 mm² or 1x 8 AWG."},{"question":"What is the operating temperature range?","answer":"The operating temperature range is -25 °C to +60 °C during operation, with a pollution degree of 3 for industrial environments."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1024-3AP60","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1024-3AP60 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}