{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1025-1BG44","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1025-1BG44","canonicalUrl":"https://aoctrl.com/siemens/3RT1025-1BG44","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1025-1BG44","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS S0 power contactor, 3RT1025-1BG44, 7.5 kW at 400 V AC-2, 15.5 A AC-4, screw terminals, 45 mm wide, DIN rail mount.","salesMarkdown":"The Siemens 3RT1025-1BG44 is a SIRIUS S0-frame power contactor rated for motor switching at 7.5 kW in AC-2 duty at 400 V, and 15.5 A in AC-4 duty at the same voltage. That AC-2 rating covers slip-ring motor reversing and inching applications where the contactor sees moderate arcing; the AC-4 figure governs plugging and jogging duty with higher electrical wear. The contactor also carries kW ratings at higher line voltages: 10 kW at 500 V and 11 kW at 690 V, which makes it usable on 480 V and 600 V class systems common in North American and export panels. DC switching capability is specified across four voltages — 10 A at 24 V, 2 A at 60 V, 1 A at 110 V, and 0.3 A at 220 V — covering battery-backed control circuits and DC motor brake coils. Main circuit terminals accept screw-type connections: solid conductors from 0.5 to 4 mm² (2x per clamp), and stranded up to 10 mm². AWG equivalents are 2x 16–12 solid, 2x 14–10 stranded, and 1x 8. The control circuit terminals use a separate solid range of 0.5–1.5 mm² and stranded 0.75–2.5 mm².","metaTitle":"Siemens 3RT1025-1BG44 SIRIUS Power Contactor, S0, 7.5 kW AC-","metaDescription":"Siemens 3RT1025-1BG44 SIRIUS S0 power contactor, 7.5 kW at 400 V AC-2, 15.5 A AC-4. Current lifecycle stage. Screw terminals, DIN rail mount. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"150 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"85 mm","Maximum":"2 000 m","At The Side":"6 mm","Rated Value":"125 V","On The Front":"IP20","Initial Value":"0.8","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP00","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Full-scale value":"1.1","Size of contactor":"S0","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 500 V rated value":"10 kW","at 690 V rated value":"11 kW","Instantaneous Contact":"2","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (1 ... 2,5 mm²), 2x (2,5 ... 6 mm²), max. 2x 10 mm²","at AC-2 at 400 V rated value":"7.5 kW","at AC-4 at 400 V rated value":"15.5 A","Closing power of magnet coil at DC":"5.4 W","Holding power of magnet coil at DC":"5.4 W","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 25 A","at AWG conductors for main contacts":"2x (16 ... 12), 2x (14 ... 10), 1x 8","With Type Of Coordination 1 Required":"fuse gL/gG: 63 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"screw-type terminals","at ambient temperature 40 °C rated value":"40 A","Type of voltage of the control supply voltage":"DC","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=197724&mlfb=3RT1025-1BG44","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1025-1BG44/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1025-1BG44","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1025-1BG44 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}