{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1026-1AP08-0MA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1026-1AP08-0MA0","canonicalUrl":"https://aoctrl.com/siemens/3RT1026-1AP08-0MA0","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1026-1AP08-0MA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S0, 3 NO main contacts, 11 kW at 400 V AC-2, 45 mm wide, screw terminals, snap-on 35 mm rail.","salesMarkdown":"It is rated for motor switching at 11 kW at 400 V in AC-2 duty, and 15.5 A at 400 V in AC-4 duty. For resistive loads (AC-1), the operating current is 10 A maximum. The auxiliary contact block provides 2 instantaneous contacts, rated at 10 A at 24 V, 6 A at 230 V, and 3 A at 400 V — enough for a PLC input or a holding circuit. Wire sizes: solid conductors from 0.5 to 4 mm² (two per terminal), stranded from 1 to 10 mm² (two per terminal). AWG equivalents: 2x 16–12, 2x 14–10, 1x 8. Pollution degree 3 means it handles conductive dust and condensation — typical for industrial control panels. IP20 on the front, IP00 at the terminals: the front is finger-safe, but the terminals need a cover or enclosure. Mechanical life is 10 million cycles typical.","metaTitle":"Siemens 3RT1026-1AP08-0MA0 SIRIUS Power Contactor, S0, 11 kW","metaDescription":"Siemens 3RT1026-1AP08-0MA0 SIRIUS power contactor, size S0, 3 NO main contacts, 11 kW at 400 V AC-2. Screw terminals, 45 mm wide, snap-on 35 mm rail. Current lifecycle stage. Sourc","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"140 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"85 mm","Maximum":"2 000 m","at 50 Hz":"0.8 ... 1.1","At The Side":"6 mm","On The Front":"IP20","1 Rated Value":"50 Hz","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP00","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Size of contactor":"S0","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"230 V","at 500 V rated value":"11 kW","at 690 V rated value":"11 kW","Instantaneous Contact":"2","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (1 ... 2,5 mm²), 2x (2,5 ... 6 mm²), max. 2x 10 mm²","at AC-2 at 400 V rated value":"11 kW","at AC-4 at 400 V rated value":"15.5 A","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 35 A","at AWG conductors for main contacts":"2x (16 ... 12), 2x (14 ... 10), 1x 8","With Type Of Coordination 1 Required":"fuse gL/gG: 100 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"screw-type terminals","at ambient temperature 40 °C rated value":"40 A","Apparent holding power of magnet coil at AC":"7.8 V·A","Apparent pick-up power of magnet coil at AC":"61 V·A","Type of voltage of the control supply voltage":"AC","Inductive power factor with closing power of the coil":"0.82","Inductive power factor with the holding power of the coil":"0.24","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=179706&mlfb=3RT1026-1AP08-0MA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1026-1AP08-0MA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RT1026-1AP08-0MA0 and get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability."},{"question":"What are the key ratings for 3RT1026-1AP08-0MA0?","answer":"It is a size S0 power contactor with 3 NO main contacts, rated 11 kW at 400 V AC-2 and 15.5 A at 400 V AC-4. It mounts on a 35 mm DIN rail, is 45 mm wide, and uses screw terminals."},{"question":"What compliance documentation does Siemens provide for this contactor?","answer":"The evidence does not list specific compliance documents. Standard SIRIUS contactors typically carry CE, UL, CSA, and RoHS declarations — confirm at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1026-1AP08-0MA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1026-1AP08-0MA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}