{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1026-1AR60","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1026-1AR60","canonicalUrl":"https://aoctrl.com/siemens/3RT1026-1AR60","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1026-1AR60","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, S0 frame, 3RT1026-1AR60, 11 kW at 500 V, screw terminals, DIN rail mount.","salesMarkdown":"The AC-4 rating for reversing or inching duty is 15.5 A at 400 V — a lower continuous current than the AC-3 figure, so factor that in if your application cycles the contactor under load. Front protection is IP20; the terminals themselves are IP00, so the contactor needs to live inside a cabinet, not out in a washdown zone. Wire sizes for the main circuit accept solid conductors from 2x 0.5 mm² up to 2x 4 mm², or stranded up to 2x 10 mm². For AWG, that's 2x 16–12 or 1x 8. The auxiliary terminals take 2x 0.5–1.5 mm² solid or 2x 0.75–2.5 mm² stranded. For Type 2 coordination (contactor remains usable after a fault), the fuse drops to gL/gG 35 A. This matters when you're specifying the short-circuit protection for the motor branch circuit. Coil operating range is 0.8–1.1 x Us at 50 Hz and 0.85–1.1 x Us at 60 Hz — standard tolerance for industrial control voltage.","metaTitle":"Siemens 3RT1026-1AR60 SIRIUS Power Contactor, S0, 11 kW at 5","metaDescription":"Siemens SIRIUS 3RT1026-1AR60 power contactor, S0 frame, 11 kW at 500 V AC. Current lifecycle stage. Screw terminals, DIN rail mount. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"91 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"45 mm","Height":"85 mm","Maximum":"2 000 m","at 50 Hz":"0.8 ... 1.1","at 60 Hz":"0.85 ... 1.1","At The Side":"6 mm","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP00","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Size of contactor":"S0","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"400 V","at 500 V rated value":"11 kW","at 60 Hz rated value":"400 ... 440 V","at 690 V rated value":"11 kW","Instantaneous Contact":"0","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (1 ... 2,5 mm²), 2x (2,5 ... 6 mm²), max. 2x 10 mm²","at AC-2 at 400 V rated value":"11 kW","at AC-4 at 400 V rated value":"15.5 A","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 35 A","at AWG conductors for main contacts":"2x (16 ... 12), 2x (14 ... 10), 1x 8","With Type Of Coordination 1 Required":"fuse gL/gG: 100 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"screw-type terminals","at ambient temperature 40 °C rated value":"40 A","Apparent holding power of magnet coil at AC":"7.5 V·A","Apparent pick-up power of magnet coil at AC":"69 V·A","Type of voltage of the control supply voltage":"AC","Inductive power factor with closing power of the coil":"0.76","Inductive power factor with the holding power of the coil":"0.28","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=61334&mlfb=3RT1026-1AR60","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1026-1AR60/alternatives.json"},"ai":{"faq":[{"question":"What are the key motor ratings for this contactor?","answer":"AC-3 duty: 11 kW at 500 V and 11 kW at 690 V. AC-2 duty: 11 kW at 400 V. AC-4 reversing duty: 15.5 A at 400 V."},{"question":"What is the physical size of the 3RT1026-1AR60?","answer":"The S0 frame measures 45 mm wide, 85 mm high, and 91 mm deep. It mounts on a 35 mm DIN rail with side-by-side spacing of 6 mm."},{"question":"What wire sizes does the main circuit accept?","answer":"Solid conductors: 2x 0.5–1.5 mm², 2x 0.75–2.5 mm², max 2x 0.75–4 mm². Stranded: 2x 1–2.5 mm², 2x 2.5–6 mm², max 2x 10 mm². AWG equivalents: 2x 16–12, 2x 14–10, or 1x 8."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1026-1AR60","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1026-1AR60 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}