{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1026-3BM40","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1026-3BM40","canonicalUrl":"https://aoctrl.com/siemens/3RT1026-3BM40","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1026-3BM40","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, 3RT1026-3BM40, S0 frame, 11 kW at 400 V AC-2, screw-type terminals, 45 mm width, DIN EN 50022 snap-on mounting.","salesMarkdown":"In AC-4 duty (inching, reversing under load), it switches 15.5 A at 400 V. The AC-12 rating of 10 A covers resistive loads. Main circuit terminals are screw-type, accepting 2x (1 to 2.5 mm²) solid/stranded, 2x (2.5 to 6 mm²), or up to 2x 10 mm². AWG equivalents: 2x (16 to 12), 2x (14 to 10), or 1x 8. The auxiliary contact terminals accept 2x (0.25 to 2.5 mm²). For Type 1 coordination (no damage under short circuit), use a gL/gG fuse rated 100 A. For Type 2 coordination (limited damage, device remains usable), the fuse drops to 35 A.","metaTitle":"Siemens SIRIUS 3RT1026-3BM40 Power Contactor, S0 Size, 11 kW","metaDescription":"Siemens SIRIUS 3RT1026-3BM40 power contactor, S0 frame, 11 kW at 400 V AC-2, screw terminals, DIN rail mount. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"100 mm","Solid":"2x (0.25 ... 2.5 mm²)","Width":"45 mm","Height":"85 mm","Maximum":"2 000 m","At The Side":"6 mm","Rated Value":"220 V","On The Front":"IP20","Initial Value":"0.8","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Of The Terminal":"IP00","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Full-scale value":"1.1","Size of contactor":"S0","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 500 V rated value":"11 kW","at 690 V rated value":"11 kW","Instantaneous Contact":"0","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (1 ... 2,5 mm²), 2x (2,5 ... 6 mm²), max. 2x 10 mm²","at AC-2 at 400 V rated value":"11 kW","at AC-4 at 400 V rated value":"15.5 A","Closing power of magnet coil at DC":"5.4 W","Holding power of magnet coil at DC":"5.4 W","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 35 A","at AWG conductors for main contacts":"2x (16 ... 12), 2x (14 ... 10), 1x 8","With Type Of Coordination 1 Required":"fuse gL/gG: 100 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.25 ... 1.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (24 ... 14)","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"spring-loaded terminals","at ambient temperature 40 °C rated value":"40 A","Finely Stranded Without Core End Processing":"2x (0.25 ... 2.5 mm²)","Type of voltage of the control supply voltage":"DC","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=173905&mlfb=3RT1026-3BM40","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1026-3BM40/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for this contactor?","answer":"AC-2 motor power: 11 kW at 400 V. AC-4 switching current: 15.5 A at 400 V. AC-12 resistive current: 10 A. Coil draw: 5.4 W DC. Operating temperature: -25 to +60 °C."},{"question":"Does it mount on standard DIN rail?","answer":"Yes, screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022. Panel width is 45 mm."},{"question":"What wire sizes does the main circuit accept?","answer":"Screw terminals accept 2x (1 to 2.5 mm²), 2x (2.5 to 6 mm²), or up to 2x 10 mm² solid/stranded. AWG: 2x (16 to 12), 2x (14 to 10), or 1x 8."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1026-3BM40","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1026-3BM40 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}