{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1033-1AV60","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1033-1AV60","canonicalUrl":"https://aoctrl.com/siemens/3RT1033-1AV60","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1033-1AV60","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT1033-1AV60 power contactor, S2 frame, screw-type terminals, 15 kW AC-2 at 400 V, 55 mm wide.","salesMarkdown":"It is rated 15 kW at AC-2 duty at 400 V, which covers standard slip-ring motor applications, and 15.5 A at AC-4 at 400 V for reversing or inching duty where the contactor makes and breaks stalled-rotor current. The 55 mm width and 112 mm height fit the standard S2 footprint on a 35 mm DIN rail per DIN EN 50022, with screw and snap-on mounting. AC-4 at 400 V: 15.5 A — this is the full-load current for reversing and plugging duty; if your application cycles the contactor under load at standstill, this is the number that keeps the arc chute from overheating. The contactor is rated for 1 000 operations per hour at AC-3, 750 at AC-2, and 250 at AC-4 — the mechanical life is 10 million cycles typical, but the electrical life depends on which duty class you run. Wire termination: the main circuit uses screw-type terminals accepting 2x 0.75–25 mm² stranded or 2x 0.5–4 mm² solid. That covers most panel wiring up to 16 mm² at 40 °C ambient.","metaTitle":"Siemens SIRIUS 3RT1033-1AV60 Power Contactor, S2 Frame, 15 k","metaDescription":"Siemens SIRIUS 3RT1033-1AV60 power contactor, S2 frame size, rated 15 kW at AC-2 400 V. Current production status. Screw terminals, DIN rail mount. Source to order via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"115 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"55 mm","at AC":"7 ... 20 ms","Height":"112 mm","Stranded":"2x (0.75 ... 25 mm²)","at 60 Hz":"0.8 ... 1.1","Arcing Time":"10 ... 15 ms","On The Front":"IP20","1 Rated Value":"60 Hz","During Storage":"-55 ... +80 °C","Of The Terminal":"IP00","at AC-1 maximum":"1 200 1/h","at AC-2 maximum":"750 1/h","at AC-3 maximum":"1 000 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Size Of Contactor":"S2","Solid Or Stranded":"2x (0.75 ... 16 mm²)","Product Brand Name":"SIRIUS","Degree Of Pollution":"3","Product Designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 500 V rated value":"11 kW","at 60 Hz rated value":"480 V","at 690 V rated value":"9.5 kW","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","at AC-2 at 400 V rated value":"15 kW","at AC-4 at 400 V rated value":"15.5 A","Substance Prohibitance (Date)":"05/01/2012","at 40 °C minimum permissible":"16 mm²","at 60 °C minimum permissible":"10 mm²","Insulation Voltage Rated Value":"690 V","at 230 V at 60 °C rated value":"15 kW","at 690 V at 60 °C rated value":"40 kW","at AWG cables for main contacts":"2x (18 ... 2)","For Auxiliary And Control Circuit":"screw-type terminals","With Type Of Assignment 2 Required":"fuse gL/gG: 63 A","Surge Voltage Resistance Rated Value":"6 kV","With Type Of Coordination 1 Required":"fuse gL/gG: 125 A","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","operational current at AC-12 maximum":"10 A","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","Thermal Short-Time Current Limited To 10 S":"200 A","Finely Stranded Without Core End Processing":"2x (0.75 ... 16 mm²)","apparent holding power of magnet coil at AC":"10.1 VA","apparent pick-up power of magnet coil at AC":"120 VA","Type Of Voltage Of The Control Supply Voltage":"AC","Required Spacing For Grounded Parts At The Side":"6 mm","contact rating of auxiliary contacts according to UL":"A600 / Q600","Inductive Power Factor With Closing Power Of The Coil":"0.7","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Inductive Power Factor With The Holding Power Of The Coil":"0.42","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"0","number of NO contacts for auxiliary contacts instantaneous contact":"0","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=286054&mlfb=3RT1033-1AV60","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1033-1AV60/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional second-source to the 3RT1033-1AV60?","answer":"The 3RT1034-1AN60-1AA0 is a peer in the SIRIUS family, but it is a different variant with a different coil voltage and terminal arrangement. The 3RT1033-1AV60 is the active standard order code; do not substitute without verifying the coil rating and wiring diagram against your panel."},{"question":"What are the key ratings for the 3RT1033-1AV60?","answer":"Rated 15 kW at AC-2 400 V for motor duty, 15.5 A at AC-4 400 V for reversing duty. Frame size S2, 55 mm wide, screw terminals, 35 mm DIN rail mount."},{"question":"What compliance documentation is available for the 3RT1033-1AV60?","answer":"The product carries a substance prohibitance date of May 1, 2012, indicating RoHS compliance. Standard Siemens declarations (CE, UL, CSA) are provided with the unit."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1033-1AV60","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1033-1AV60 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}