{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1034-1AP00-ZW98","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1034-1AP00-ZW98","canonicalUrl":"https://aoctrl.com/siemens/3RT1034-1AP00-ZW98","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1034-1AP00-ZW98","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT1034-1AP00-ZW98 power contactor, Size S2, 50 Hz rated, screw-type terminals, IP20 front / IP00 terminal, 115 mm depth, 55 mm width, 112 mm height.","salesMarkdown":"## Siemens SIRIUS 3RT1034-1AP00-ZW98 — Size S2 Power Contactor Rated for 50 Hz operation, the contactor delivers 18.5 kW at 500 V and 10 kW at 690 V. In AC-3 duty (motor starting under load), it's rated for up to 1,000 operations per hour; AC-4 (plugging/reversing) drops to 250 ops/h. AC-4 at 400 V is rated at 29 A — that's the inching or jogging current limit, not continuous motor current. The main current circuit uses screw-type terminals, accepting solid conductors up to 2x (0.5–1.5 mm²) or 2x (0.75–2.5 mm²), and stranded up to 2x (0.75–25 mm²). Keep the panel door interlocked or use finger-safe shrouds if maintenance access is live. The contactor occupies a 55 mm wide DIN-rail footprint (Size S2), with a depth of 115 mm and height of 112 mm. Side-by-side mounting is supported. AC-1 allows 1,200 ops/h, AC-3 1,000 ops/h, AC-4 250 ops/h.","metaTitle":"Siemens 3RT1034-1AP00-ZW98 SIRIUS Power Contactor, Size S2,","metaDescription":"Siemens SIRIUS 3RT1034-1AP00-ZW98 power contactor, Size S2, 50 Hz, screw terminals, IP20 front, DIN rail mount. Sourced to order. Request quote for current pricing and availability","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"115 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"55 mm","at AC":"7 ... 20 ms","Height":"112 mm","Stranded":"2x (0.75 ... 25 mm²)","at 50 Hz":"0.8 ... 1.1","Arcing Time":"10 ... 15 ms","On The Front":"IP20","1 Rated Value":"50 Hz","During Storage":"-55 ... +80 °C","Of The Terminal":"IP00","at AC-1 maximum":"1 200 1/h","at AC-2 maximum":"750 1/h","at AC-3 maximum":"1 000 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Size Of Contactor":"S2","Solid Or Stranded":"2x (0.75 ... 16 mm²)","Product Brand Name":"SIRIUS","Degree Of Pollution":"3","Product Designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"230 V","at 500 V rated value":"18.5 kW","at 690 V rated value":"10 kW","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","at AC-2 at 400 V rated value":"15 kW","at AC-4 at 400 V rated value":"29 A","Substance Prohibitance (Date)":"05/01/2012","at 40 °C minimum permissible":"16 mm²","at 60 °C minimum permissible":"10 mm²","Insulation Voltage Rated Value":"690 V","at 230 V at 60 °C rated value":"18 kW","at 690 V at 60 °C rated value":"54 kW","at AWG cables for main contacts":"2x (18 ... 2)","For Auxiliary And Control Circuit":"screw-type terminals","With Type Of Assignment 2 Required":"fuse gL/gG: 63 A","Surge Voltage Resistance Rated Value":"6 kV","With Type Of Coordination 1 Required":"fuse gL/gG: 125 A","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","operational current at AC-12 maximum":"10 A","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","Thermal Short-Time Current Limited To 10 S":"320 A","Finely Stranded Without Core End Processing":"2x (0.75 ... 16 mm²)","apparent holding power of magnet coil at AC":"9.7 VA","apparent pick-up power of magnet coil at AC":"104 VA","Type Of Voltage Of The Control Supply Voltage":"AC","Required Spacing For Grounded Parts At The Side":"6 mm","contact rating of auxiliary contacts according to UL":"A600 / Q600","Inductive Power Factor With Closing Power Of The Coil":"0.78","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Inductive Power Factor With The Holding Power Of The Coil":"0.42","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"0","number of NO contacts for auxiliary contacts instantaneous contact":"0","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=194211&mlfb=3RT1034-1AP00-ZW98","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1034-1AP00-ZW98/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional second-source for 3RT1034-1AP00-ZW98?","answer":"The 3RT5034-1BW40 is a Size S2 contactor in the same SIRIUS family, but it's a 3RT5 generation part with different coil ratings and auxiliary configurations. The 3RT1034-1AP00-ZW98 is a 3RT1 generation part. They are not drop-in interchangeable without verifying coil voltage, terminal layout, and accessory compatibility. For a direct replacement, stick with the same order code or consult Siemens cross-reference documentation."},{"question":"What are the key dimensions of 3RT1034-1AP00-ZW98?","answer":"The contactor measures 115 mm depth, 55 mm width, and 112 mm height. It mounts on a 35 mm DIN rail per EN 50022 with screw and snap-on fastening."},{"question":"What wire sizes does the 3RT1034-1AP00-ZW98 accept?","answer":"Solid conductors: 2x (0.5–1.5 mm²), 2x (0.75–2.5 mm²), max 2x (0.75–4 mm²). Stranded: 2x (0.75–25 mm²). Solid or stranded: 2x (0.75–16 mm²). All connections use screw-type terminals on the main current circuit."},{"question":"Will 3RT1034-1AP00-ZW98 drop into a panel specified for 3RT5034-1BW40?","answer":"No, not without verification. The 3RT1034 is a 3RT1 generation contactor; the 3RT5034 is a 3RT5 generation. While both are Size S2, differences in coil rating, auxiliary contact arrangement, and terminal layout mean they are not direct mechanical or electrical substitutes. Check the panel wiring diagram and Siemens compatibility notes before substitution."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1034-1AP00-ZW98","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1034-1AP00-ZW98 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}