{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1034-1AR60-ZX95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1034-1AR60-ZX95","canonicalUrl":"https://aoctrl.com/siemens/3RT1034-1AR60-ZX95","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1034-1AR60-ZX95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S2, 3RT1034-1AR60-ZX95, 15 kW at 400 V AC-2, screw-type terminals, 55 mm width, DIN rail mount.","salesMarkdown":"It is rated for 15 kW at 400 V in AC-2 duty, which covers slip-ring motor starting and plugging applications, and 18.5 kW at 500 V in AC-3 for standard squirrel-cage motors. The coil operates on 50 Hz at 400 V or 60 Hz at 400 to 440 V, with an operating range of 0.8 to 1.1 times rated voltage at 50 Hz and 0.85 to 1.1 at 60 Hz. Dimensions: 55 mm wide, 112 mm high, 115 mm deep. Side-by-side mounting is permitted, which saves panel width when grouping multiple contactors. Main circuit connections use screw-type terminals; wire ranges accept solid conductors from 2x 0.5 to 4 mm² and stranded from 2x 0.75 to 25 mm². ## Environmental and protection ratings Front face carries IP20 finger protection; terminals are IP00, so the contactor needs to be housed in a panel or enclosure with a higher overall IP rating. ## Switching performance and auxiliary ratings Rated for 1,200 operations per hour in AC-1, 750 in AC-2, 1,000 in AC-3, and 250 in AC-4. Auxiliary contacts are rated for 10 A at 24 V, 2 A at 60 V, 1 A at 110 V, 0.3 A at 220 V, 6 A at 230 V, and 3 A at 400 V.","metaTitle":"Siemens 3RT1034-1AR60-ZX95 SIRIUS Power Contactor, S2, 15 kW","metaDescription":"Siemens SIRIUS 3RT1034-1AR60-ZX95 power contactor, size S2, rated 15 kW at 400 V AC-2. Active production. Screw terminals, DIN rail mount. RFQ for pricing.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"115 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"55 mm","at AC":"7 ... 20 ms","Height":"112 mm","Stranded":"2x (0.75 ... 25 mm²)","at 50 Hz":"0.8 ... 1.1","at 60 Hz":"0.85 ... 1.1","Arcing Time":"10 ... 15 ms","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","During Storage":"-55 ... +80 °C","Of The Terminal":"IP00","at AC-1 maximum":"1 200 1/h","at AC-2 maximum":"750 1/h","at AC-3 maximum":"1 000 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Size Of Contactor":"S2","Solid Or Stranded":"2x (0.75 ... 16 mm²)","Product Brand Name":"SIRIUS","Degree Of Pollution":"3","Product Designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"400 V","at 500 V rated value":"18.5 kW","at 60 Hz rated value":"400 ... 440 V","at 690 V rated value":"10 kW","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","at AC-2 at 400 V rated value":"15 kW","at AC-4 at 400 V rated value":"29 A","Substance Prohibitance (Date)":"05/01/2012","at 40 °C minimum permissible":"16 mm²","at 60 °C minimum permissible":"10 mm²","Insulation Voltage Rated Value":"690 V","at 230 V at 60 °C rated value":"18 kW","at 690 V at 60 °C rated value":"54 kW","at AWG cables for main contacts":"2x (18 ... 2)","For Auxiliary And Control Circuit":"screw-type terminals","With Type Of Assignment 2 Required":"fuse gL/gG: 63 A","Surge Voltage Resistance Rated Value":"6 kV","With Type Of Coordination 1 Required":"fuse gL/gG: 125 A","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","operational current at AC-12 maximum":"10 A","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","Thermal Short-Time Current Limited To 10 S":"320 A","Finely Stranded Without Core End Processing":"2x (0.75 ... 16 mm²)","apparent holding power of magnet coil at AC":"10.1 VA","apparent pick-up power of magnet coil at AC":"120 VA","Type Of Voltage Of The Control Supply Voltage":"AC","Required Spacing For Grounded Parts At The Side":"6 mm","contact rating of auxiliary contacts according to UL":"A600 / Q600","Inductive Power Factor With Closing Power Of The Coil":"0.7","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Inductive Power Factor With The Holding Power Of The Coil":"0.42","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"0","number of NO contacts for auxiliary contacts instantaneous contact":"0","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=466160&mlfb=3RT1034-1AR60-ZX95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1034-1AR60-ZX95/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional alternative to 3RT1034-1AR60-ZX95?","answer":"The peer 3RT1034-1AN60-1AA0 is a close functional match within the same SIRIUS S2 size, but the -ZX95 variant carries a specific coil voltage (400 V at 50 Hz, 400-440 V at 60 Hz) and auxiliary contact configuration. Verify coil compatibility before substituting — the -1AN60-1AA0 uses a different coil voltage range."},{"question":"What are the key dimensions of this contactor?","answer":"Width is 55 mm, height is 112 mm, and depth is 115 mm. It mounts on 35 mm DIN rail per EN 50022."},{"question":"What wire sizes does the main circuit accept?","answer":"Solid conductors: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), max 2x (0.75 to 4 mm²). Stranded: 2x (0.75 to 25 mm²). Solid or stranded: 2x (0.75 to 16 mm²)."},{"question":"Will 3RT1034-1AR60-ZX95 drop into a panel designed for 3RT1034-1AN60-1AA0 without rewiring?","answer":"Mechanically yes — same S2 size, same DIN rail footprint, same screw terminal locations. Electrically, verify the coil voltage: the -ZX95 uses 400 V at 50 Hz / 400-440 V at 60 Hz, while the -1AN60-1AA0 uses a different coil. If coil voltages match, no rewiring is needed for the power circuit."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1034-1AR60-ZX95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1034-1AR60-ZX95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}