{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1034-1AV60","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1034-1AV60","canonicalUrl":"https://aoctrl.com/siemens/3RT1034-1AV60","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1034-1AV60","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S2, 3RT1034-1AV60, screw-type terminals, 55 mm width, 115 mm depth, snap-on 35 mm DIN rail.","salesMarkdown":"Rated motor power: 18.5 kW at 500 V (60 Hz) and 10 kW at 690 V (60 Hz), and 15 kW at 400 V under AC-2 duty. That covers standard three-phase induction motors on 400 V, 480 V, and 690 V grids. Auxiliary contacts handle 10 A at 24 V, 6 A at 230 V, and 3 A at 400 V — enough for control-circuit interlocking or status feedback. The coil hold-in range is 0.8 to 1.1 times rated voltage at 60 Hz, with an arcing time of 10 to 15 ms. The contactor is 55 mm wide and 115 mm deep, with a height of 112 mm. It mounts side-by-side without derating (side-by-side mounting is permitted). For a panel builder, that means you can land a 16 mm² stranded cable on the main circuit and still have room for auxiliary wiring.","metaTitle":"Siemens 3RT1034-1AV60 SIRIUS Power Contactor, S2, 55 mm, 115","metaDescription":"Siemens SIRIUS 3RT1034-1AV60 power contactor, size S2, 55 mm wide, 115 mm deep. Screw/snap-on DIN rail mount. Rated for 18.5 kW at 500 V, 10 kW at 690 V. Current lifecycle, sourced","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"115 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"55 mm","at AC":"7 ... 20 ms","Height":"112 mm","Stranded":"2x (0.75 ... 25 mm²)","at 60 Hz":"0.8 ... 1.1","Arcing Time":"10 ... 15 ms","On The Front":"IP20","1 Rated Value":"60 Hz","During Storage":"-55 ... +80 °C","Of The Terminal":"IP00","at AC-1 maximum":"1 200 1/h","at AC-2 maximum":"750 1/h","at AC-3 maximum":"1 000 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Size Of Contactor":"S2","Solid Or Stranded":"2x (0.75 ... 16 mm²)","Product Brand Name":"SIRIUS","Degree Of Pollution":"3","Product Designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 500 V rated value":"18.5 kW","at 60 Hz rated value":"480 V","at 690 V rated value":"10 kW","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","at AC-2 at 400 V rated value":"15 kW","at AC-4 at 400 V rated value":"29 A","Substance Prohibitance (Date)":"05/01/2012","at 40 °C minimum permissible":"16 mm²","at 60 °C minimum permissible":"10 mm²","Insulation Voltage Rated Value":"690 V","at 230 V at 60 °C rated value":"18 kW","at 690 V at 60 °C rated value":"54 kW","at AWG cables for main contacts":"2x (18 ... 2)","For Auxiliary And Control Circuit":"screw-type terminals","With Type Of Assignment 2 Required":"fuse gL/gG: 63 A","Surge Voltage Resistance Rated Value":"6 kV","With Type Of Coordination 1 Required":"fuse gL/gG: 125 A","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","operational current at AC-12 maximum":"10 A","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","Thermal Short-Time Current Limited To 10 S":"320 A","Finely Stranded Without Core End Processing":"2x (0.75 ... 16 mm²)","apparent holding power of magnet coil at AC":"10.1 VA","apparent pick-up power of magnet coil at AC":"120 VA","Type Of Voltage Of The Control Supply Voltage":"AC","Required Spacing For Grounded Parts At The Side":"6 mm","contact rating of auxiliary contacts according to UL":"A600 / Q600","Inductive Power Factor With Closing Power Of The Coil":"0.7","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Inductive Power Factor With The Holding Power Of The Coil":"0.42","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"0","number of NO contacts for auxiliary contacts instantaneous contact":"0","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=535073&mlfb=3RT1034-1AV60","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1034-1AV60/alternatives.json"},"ai":{"faq":[{"question":"When sourcing 3RT1034-1AV60, what's the closest functional second-source?","answer":"The 3RT5034-1AR60 is a similar SIRIUS contactor in the same size S2 frame, but it uses spring-cage terminals instead of screw-type. Check terminal compatibility before substituting."},{"question":"What is 3RT1034-1AV60's listed depth?","answer":"The depth is 115 mm."},{"question":"What solid wire sizes does 3RT1034-1AV60 accept?","answer":"Solid wire: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), and max 2x (0.75 to 4 mm²)."},{"question":"Will 3RT1034-1AV60 drop into a panel specified around 3RT5034-1AR60 without rewiring?","answer":"The physical footprint (55 mm width, 115 mm depth, DIN rail mount) is the same, but the 3RT5034-1AR60 uses spring-cage terminals. If the panel is wired for screw terminals, you may need to change lugs or ferrules."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1034-1AV60","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1034-1AV60 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}