{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1034-1BN40","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1034-1BN40","canonicalUrl":"https://aoctrl.com/siemens/3RT1034-1BN40","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1034-1BN40","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, S2 frame, 3RT1034-1BN40, 18.5 kW AC-3 at 500 V, screw terminals, DIN rail mount.","salesMarkdown":"The 130 mm depth leaves clearance for wiring ducts or adjacent components. The headline motor ratings are 18.5 kW at 500 V and 10 kW at 690 V under AC-3 duty — that is the category for starting squirrel-cage motors and disconnecting them while running, which covers most conveyor, pump, and fan applications. For AC-2 duty (slip-ring motors, moderate overloads) it is rated 15 kW at 400 V. For AC-4 (plugging, inching, reversing) it handles 29 A at 400 V — a tougher thermal cycle, so the switching frequency drops to 250 operations per hour versus 1 000 for AC-3. The auxiliary contact ratings cover a range of control voltages: 10 A at 24 V DC, 6 A at 230 V AC, and 0.3 A at 220 V DC — enough for PLC inputs or relay coils in the control circuit. ## Environmental Fit and Compliance The front face carries IP20 finger protection; the terminals are IP00, so the contactor expects enclosure protection around the wiring zone.","metaTitle":"Siemens 3RT1034-1BN40 SIRIUS Power Contactor, S2 Frame, 18.5","metaDescription":"Siemens SIRIUS 3RT1034-1BN40 power contactor, S2 size, 18.5 kW AC-3 at 500 V, 10 kW at 690 V. Current lifecycle stage. Screw terminals, DIN rail mount. RoHS compliant. Sourced to o","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"130 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"55 mm","at DC":"20 ... 30 ms","Height":"112 mm","Stranded":"2x (0.75 ... 25 mm²)","Arcing Time":"10 ... 15 ms","Rated Value":"250 V","On The Front":"IP20","Initial Value":"0.8","During Storage":"-55 ... +80 °C","Of The Terminal":"IP00","at AC-1 maximum":"1 200 1/h","at AC-2 maximum":"750 1/h","at AC-3 maximum":"1 000 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Full-Scale Value":"1.1","Size Of Contactor":"S2","Solid Or Stranded":"2x (0.75 ... 16 mm²)","Product Brand Name":"SIRIUS","Degree Of Pollution":"3","Product Designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 500 V rated value":"18.5 kW","at 690 V rated value":"10 kW","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","at AC-2 at 400 V rated value":"15 kW","at AC-4 at 400 V rated value":"29 A","Substance Prohibitance (Date)":"05/01/2012","at 40 °C minimum permissible":"16 mm²","at 60 °C minimum permissible":"10 mm²","Insulation Voltage Rated Value":"690 V","at 230 V at 60 °C rated value":"18 kW","at 690 V at 60 °C rated value":"54 kW","at AWG cables for main contacts":"2x (18 ... 2)","For Auxiliary And Control Circuit":"screw-type terminals","With Type Of Assignment 2 Required":"fuse gL/gG: 63 A","closing power of magnet coil at DC":"13.3 W","holding power of magnet coil at DC":"13.3 W","Surge Voltage Resistance Rated Value":"6 kV","With Type Of Coordination 1 Required":"fuse gL/gG: 125 A","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","operational current at AC-12 maximum":"10 A","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","Thermal Short-Time Current Limited To 10 S":"320 A","Finely Stranded Without Core End Processing":"2x (0.75 ... 16 mm²)","Type Of Voltage Of The Control Supply Voltage":"DC","Required Spacing For Grounded Parts At The Side":"6 mm","contact rating of auxiliary contacts according to UL":"A600 / Q600","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"0","number of NO contacts for auxiliary contacts instantaneous contact":"0","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=752824&mlfb=3RT1034-1BN40","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1034-1BN40/alternatives.json"},"ai":{"faq":[{"question":"What are the key motor ratings for this contactor?","answer":"AC-3 duty: 18.5 kW at 500 V and 10 kW at 690 V. AC-2 at 400 V: 15 kW. AC-4 at 400 V: 29 A."},{"question":"What is the physical size and mounting method?","answer":"S2 frame, 55 mm wide, 112 mm high, 130 mm deep. Screw and snap-on mounting onto 35 mm DIN rail per DIN EN 50022."},{"question":"What compliance documentation is available?","answer":"RoHS compliance is confirmed with a substance prohibition date of 05/01/2012. The contactor carries IP20 front protection and is rated for pollution degree 3."},{"question":"What wire sizes does the screw terminal accept?","answer":"Solid: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), max 2x (0.75 to 4 mm²). Stranded: 2x (0.75 to 25 mm²)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1034-1BN40","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1034-1BN40 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}