{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1034-3AG10","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1034-3AG10","canonicalUrl":"https://aoctrl.com/siemens/3RT1034-3AG10","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1034-3AG10","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RT1034-3AG10 power contactor, size S2, screw-type terminals, 18.5 kW at 500 V AC-3, 55 mm wide, DIN rail mount.","salesMarkdown":"It is rated for 18.5 kW at 500 V in AC-3 duty, which is the standard category for starting and stopping squirrel-cage motors — that 18.5 kW figure is the one that governs the real motor load it can handle, not a resistive rating. At 400 V AC-2 (slip-ring motors, moderate overloads) it is rated for 15 kW, and in AC-4 duty (plugging, inching) it handles 29 A at 400 V. Screw-type terminals on the main current circuit accept 2x (0.75... 25 mm²) stranded or 2x (0.25... 2.5 mm²) solid. The SIRIUS series is Siemens' standard industrial contactor line, so supply continuity is the norm.","metaTitle":"Siemens 3RT1034-3AG10 SIRIUS Power Contactor, S2, 18.5 kW at","metaDescription":"Siemens 3RT1034-3AG10 SIRIUS power contactor, size S2, rated 18.5 kW at 500 V AC-3. Current lifecycle stage. Screw terminals, DIN rail mount. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"115 mm","Solid":"2x (0.25 ... 2.5 mm²)","Width":"55 mm","at AC":"7 ... 20 ms","Height":"112 mm","Stranded":"2x (0.75 ... 25 mm²)","at 60 Hz":"0.8 ... 1.1","Arcing Time":"10 ... 15 ms","On The Front":"IP20","1 Rated Value":"60 Hz","2 Rated Value":"50 Hz","During Storage":"-55 ... +80 °C","Of The Terminal":"IP00","at AC-1 maximum":"1 200 1/h","at AC-2 maximum":"750 1/h","at AC-3 maximum":"1 000 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Size Of Contactor":"S2","Solid Or Stranded":"2x (0.75 ... 16 mm²)","Product Brand Name":"SIRIUS","Degree Of Pollution":"3","Product Designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"100 V","at 500 V rated value":"18.5 kW","at 60 Hz rated value":"110 V","at 690 V rated value":"10 kW","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","at AC-2 at 400 V rated value":"15 kW","at AC-4 at 400 V rated value":"29 A","Substance Prohibitance (Date)":"05/01/2012","at 40 °C minimum permissible":"16 mm²","at 60 °C minimum permissible":"10 mm²","Insulation Voltage Rated Value":"690 V","at 230 V at 60 °C rated value":"18 kW","at 690 V at 60 °C rated value":"54 kW","at AWG cables for main contacts":"2x (18 ... 2)","For Auxiliary And Control Circuit":"spring-loaded terminals","With Type Of Assignment 2 Required":"fuse gL/gG: 63 A","Surge Voltage Resistance Rated Value":"6 kV","With Type Of Coordination 1 Required":"fuse gL/gG: 125 A","at AWG cables for auxiliary contacts":"2x (24 ... 14)","operational current at AC-12 maximum":"10 A","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.25 ... 1.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","Thermal Short-Time Current Limited To 10 S":"320 A","Finely Stranded Without Core End Processing":"2x (0.25 ... 2.5 mm²)","apparent holding power of magnet coil at AC":"10.1 VA","apparent pick-up power of magnet coil at AC":"120 VA","Type Of Voltage Of The Control Supply Voltage":"AC","Required Spacing For Grounded Parts At The Side":"6 mm","contact rating of auxiliary contacts according to UL":"A600 / Q600","Inductive Power Factor With Closing Power Of The Coil":"0.7","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Inductive Power Factor With The Holding Power Of The Coil":"0.42","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"0","number of NO contacts for auxiliary contacts instantaneous contact":"0","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=456218&mlfb=3RT1034-3AG10","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1034-3AG10/alternatives.json"},"ai":{"faq":[{"question":"What are the key motor ratings for this contactor?","answer":"The key motor ratings are 18.5 kW at 500 V AC-3, 15 kW at 400 V AC-2, and 29 A at 400 V AC-4. The AC-3 rating is the one that governs standard motor starting."},{"question":"What is the depth of this contactor?","answer":"The depth is 115 mm, with a width of 55 mm and height of 112 mm."},{"question":"What wire sizes does the screw terminal accept?","answer":"The main circuit screw terminals accept 2x (0.75... 25 mm²) stranded or 2x (0.25... 2.5 mm²) solid conductors."},{"question":"What is the operating temperature range?","answer":"During operation the range is -25 to +60 °C; storage range is -55 to +80 °C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1034-3AG10","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1034-3AG10 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}