{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1034-3AP06-ZX95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1034-3AP06-ZX95","canonicalUrl":"https://aoctrl.com/siemens/3RT1034-3AP06-ZX95","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1034-3AP06-ZX95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S2, order code 3RT1034-3AP06-ZX95, rated 15 kW at AC-2 400 V, 29 A at AC-4 400 V, screw-type terminals, snap-on DIN rail mounting.","salesMarkdown":"The 3RT1034-3AP06-ZX95: The AC-2 rating of 15 kW at 400 V defines its capability for switching slip-ring motor loads, where moderate inrush and frequent operation are expected. The AC-4 rating of 29 A at 400 V covers plugging and inching duty, the most severe switching condition for a contactor — this figure governs the maximum current the contacts can interrupt during reverse or jogging cycles. For standard squirrel-cage motor starting (AC-3), the contactor is rated at 18.5 kW at 500 V and 10 kW at 690 V, giving flexibility across common industrial voltage levels. Main circuit terminals are screw-type, accepting solid conductors from 0.25 to 2.5 mm² (2x) and stranded conductors up to 25 mm² (2x). The minimum permissible conductor cross-section at 40 °C is 16 mm², which is relevant for sizing the main power wiring. Rated for degree of pollution 3 (conductive pollution typical in industrial enclosures), with IP20 protection on the front and IP00 at the terminals. Storage temperature range spans -55 to +80 °C. The substance prohibitance date of 05/01/2012 aligns with RoHS compliance requirements.","metaTitle":"Siemens 3RT1034-3AP06-ZX95 SIRIUS Power Contactor, S2, 15 kW","metaDescription":"Siemens SIRIUS 3RT1034-3AP06-ZX95 power contactor, size S2, rated 15 kW at AC-2 400 V and 29 A at AC-4 400 V. Current lifecycle stage. Screw terminals, snap-on DIN rail mount. RFQ","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"115 mm","Solid":"2x (0.25 ... 2.5 mm²)","Width":"75 mm","at AC":"7 ... 20 ms","Height":"112 mm","Stranded":"2x (0.75 ... 25 mm²)","at 50 Hz":"0.8 ... 1.1","Arcing Time":"10 ... 15 ms","On The Front":"IP20","1 Rated Value":"50 Hz","During Storage":"-55 ... +80 °C","Of The Terminal":"IP00","at AC-1 maximum":"1 200 1/h","at AC-2 maximum":"750 1/h","at AC-3 maximum":"1 000 1/h","at AC-4 maximum":"250 1/h","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Size Of Contactor":"S2","Solid Or Stranded":"2x (0.75 ... 16 mm²)","Product Brand Name":"SIRIUS","Degree Of Pollution":"3","Product Designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"230 V","at 500 V rated value":"18.5 kW","at 690 V rated value":"10 kW","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","at AC-2 at 400 V rated value":"15 kW","at AC-4 at 400 V rated value":"29 A","Substance Prohibitance (Date)":"05/01/2012","at 40 °C minimum permissible":"16 mm²","at 60 °C minimum permissible":"10 mm²","Insulation Voltage Rated Value":"690 V","at 230 V at 60 °C rated value":"18 kW","at 690 V at 60 °C rated value":"54 kW","at AWG cables for main contacts":"2x (18 ... 2)","For Auxiliary And Control Circuit":"spring-loaded terminals","With Type Of Assignment 2 Required":"fuse gL/gG: 63 A","Surge Voltage Resistance Rated Value":"6 kV","With Type Of Coordination 1 Required":"fuse gL/gG: 125 A","at AWG cables for auxiliary contacts":"2x (24 ... 14)","operational current at AC-12 maximum":"10 A","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.25 ... 1.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","Thermal Short-Time Current Limited To 10 S":"320 A","Finely Stranded Without Core End Processing":"2x (0.25 ... 2.5 mm²)","apparent holding power of magnet coil at AC":"9.7 VA","apparent pick-up power of magnet coil at AC":"104 VA","Type Of Voltage Of The Control Supply Voltage":"AC","Required Spacing For Grounded Parts At The Side":"6 mm","contact rating of auxiliary contacts according to UL":"A600 / Q600","Inductive Power Factor With Closing Power Of The Coil":"0.78","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Inductive Power Factor With The Holding Power Of The Coil":"0.42","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"2","number of NO contacts for auxiliary contacts instantaneous contact":"2","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=510043&mlfb=3RT1034-3AP06-ZX95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1034-3AP06-ZX95/alternatives.json"},"ai":{"faq":[{"question":"What are the key power ratings for this contactor?","answer":"The contactor is rated 15 kW at AC-2 400 V, 29 A at AC-4 400 V, 18.5 kW at AC-3 500 V, and 10 kW at AC-3 690 V."},{"question":"How is this contactor mounted?","answer":"It mounts via screw fixing or snap-on onto a 35 mm DIN rail per EN 50022, and side-by-side mounting is permitted."},{"question":"What conductor sizes does the screw terminal accept?","answer":"The main circuit terminals accept solid conductors 2x (0.25 to 2.5 mm²) and stranded conductors 2x (0.75 to 25 mm²). The minimum permissible cross-section at 40 °C is 16 mm²."},{"question":"What is the operating temperature range?","answer":"The operating temperature range is -25 to +60 °C, with storage from -55 to +80 °C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1034-3AP06-ZX95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1034-3AP06-ZX95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}