{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1035-3AR60","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1035-3AR60","canonicalUrl":"https://aoctrl.com/siemens/3RT1035-3AR60","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1035-3AR60","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S2, 3RT1035-3AR60, screw-type terminals, 22 kW at 500 V AC-3, snap-on DIN rail mounting.","salesMarkdown":"## Siemens 3RT1035-3AR60 — SIRIUS Size S2 Power Contactor The Siemens 3RT1035-3AR60 is a SIRIUS-brand power contactor in frame size S2, rated for motor switching up to 22 kW at 500 V in AC-3 duty. ## Switching Performance and Mechanical Life Mechanical life is typical 10,000,000 operations — that's the no-load endurance. Under load, the electrical life depends on the duty cycle: AC-3 max switching rate is 1,000 operations per hour, AC-2 max 600 ops/h, AC-4 max 300 ops/h. For a conveyor that cycles once every 30 seconds, AC-3 at 1,000 ops/h gives you headroom; for a jogging application (AC-4), the 300 ops/h limit means you'll need to derate or accept shorter contact life. Solid wire: 2x (0.25 – 2.5 mm²). Stranded: 2x (0.75 – 25 mm²). Combined solid or stranded: 2x (0.75 – 16 mm²). Physical footprint: width 55 mm, height 112 mm, depth 115 mm. ## Coil and Auxiliary Ratings The contactor carries auxiliary contact ratings at various voltages: 24 V rated value 10 A, 60 V rated value 2 A, 110 V rated value 1 A, 220 V rated value 0.3 A, 230 V rated value 6 A, 400 V rated value 3 A. These are the make/break capacities for the auxiliary contacts — not the main power path. The 10 A at 24 V is useful for pilot duty on a 24 VDC PLC output; the 6 A at 230 V covers a typical control transformer secondary. The 0.3 A at 220 V is low — that's the DC-13 rating for a 220 VDC inductive load, which is a tough switch for any contactor.","metaTitle":"Siemens 3RT1035-3AR60 SIRIUS Power Contactor, 22 kW at 500 V","metaDescription":"Siemens SIRIUS 3RT1035-3AR60 power contactor, size S2, rated 22 kW at 500 V AC-3. Screw terminals, snap-on DIN rail. Current production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"115 mm","Solid":"2x (0.25 ... 2.5 mm²)","Width":"55 mm","at AC":"7 ... 20 ms","Height":"112 mm","Stranded":"2x (0.75 ... 25 mm²)","at 50 Hz":"0.8 ... 1.1","at 60 Hz":"0.85 ... 1.1","Arcing Time":"10 ... 15 ms","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","During Storage":"-55 ... +80 °C","Of The Terminal":"IP00","at AC-1 maximum":"1 200 1/h","at AC-2 maximum":"600 1/h","at AC-3 maximum":"1 000 1/h","at AC-4 maximum":"300 1/h","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Size Of Contactor":"S2","Solid Or Stranded":"2x (0.75 ... 16 mm²)","Product Brand Name":"SIRIUS","Degree Of Pollution":"3","Product Designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"400 V","at 500 V rated value":"22 kW","at 60 Hz rated value":"400 ... 440 V","at 690 V rated value":"11.4 kW","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","at AC-2 at 400 V rated value":"18.5 kW","at AC-4 at 400 V rated value":"35 A","Substance Prohibitance (Date)":"05/01/2012","at 40 °C minimum permissible":"16 mm²","at 60 °C minimum permissible":"16 mm²","Insulation Voltage Rated Value":"690 V","at 230 V at 60 °C rated value":"22 kW","at 690 V at 60 °C rated value":"66 kW","at AWG cables for main contacts":"2x (18 ... 2)","For Auxiliary And Control Circuit":"spring-loaded terminals","With Type Of Assignment 2 Required":"fuse gL/gG: 63 A","Surge Voltage Resistance Rated Value":"6 kV","With Type Of Coordination 1 Required":"fuse gL/gG: 125 A","at AWG cables for auxiliary contacts":"2x (24 ... 14)","operational current at AC-12 maximum":"10 A","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.25 ... 1.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","Thermal Short-Time Current Limited To 10 S":"400 A","Finely Stranded Without Core End Processing":"2x (0.25 ... 2.5 mm²)","apparent holding power of magnet coil at AC":"12.6 VA","apparent pick-up power of magnet coil at AC":"166 VA","Type Of Voltage Of The Control Supply Voltage":"AC","Required Spacing For Grounded Parts At The Side":"6 mm","contact rating of auxiliary contacts according to UL":"A600 / Q600","Inductive Power Factor With Closing Power Of The Coil":"0.71","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Inductive Power Factor With The Holding Power Of The Coil":"0.37","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"0","number of NO contacts for auxiliary contacts instantaneous contact":"0","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=367127&mlfb=3RT1035-3AR60","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1035-3AR60/alternatives.json"},"ai":{"faq":[{"question":"What is the depth of 3RT1035-3AR60?","answer":"The depth is 115 mm, measured from the DIN rail mounting surface to the furthest projection."},{"question":"What wire sizes does 3RT1035-3AR60 accept on the main terminals?","answer":"Solid wire: 2x (0.25 – 2.5 mm²). Stranded: 2x (0.75 – 25 mm²). Combined solid or stranded: 2x (0.75 – 16 mm²). Screw-type terminals."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1035-3AR60","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1035-3AR60 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}