{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1035-3AV60","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1035-3AV60","canonicalUrl":"https://aoctrl.com/siemens/3RT1035-3AV60","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1035-3AV60","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, order code 3RT1035-3AV60, S2 frame size, 480 V at 60 Hz rated coil, screw-type terminals, screw and snap-on mounting on 35 mm DIN rail.","salesMarkdown":"The S2 frame footprint — 55 mm wide, 112 mm high, 115 mm deep — fits standard DIN-rail enclosures with room for side-by-side mounting. Main circuit terminals are screw-type, accepting 2x (0.75... 25 mm²) stranded or 2x (0.75... 16 mm²) solid/stranded. The control circuit takes 2x (0.25... 2.5 mm²) solid. Minimum 16 mm² at 40 °C for the main circuit. IP20 on the front, IP00 at the terminals — wire into the panel, not exposed to touch. ## Duty Ratings and Switching Performance The AC-1 resistive load rating supports 1,200 operations per hour; AC-3 motor switching drops to 1,000 ops/h; AC-4 severe duty is 300 ops/h. DC switching capability is provided: 10 A at 24 V, 2 A at 60 V, 1 A at 110 V, and 0.3 A at 220 V — useful for DC control circuits or small DC motor loads.","metaTitle":"Siemens 3RT1035-3AV60 SIRIUS Power Contactor, S2 Size, 480V","metaDescription":"Siemens 3RT1035-3AV60 SIRIUS power contactor, S2 size, 480V 60Hz, 22kW at 500V, AC-4 35A. Current lifecycle stage. Screw & snap-on DIN rail mount. IP20 front. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"115 mm","Solid":"2x (0.25 ... 2.5 mm²)","Width":"55 mm","at AC":"7 ... 20 ms","Height":"112 mm","Stranded":"2x (0.75 ... 25 mm²)","at 60 Hz":"0.8 ... 1.1","Arcing Time":"10 ... 15 ms","On The Front":"IP20","1 Rated Value":"60 Hz","During Storage":"-55 ... +80 °C","Of The Terminal":"IP00","at AC-1 maximum":"1 200 1/h","at AC-2 maximum":"600 1/h","at AC-3 maximum":"1 000 1/h","at AC-4 maximum":"300 1/h","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Size Of Contactor":"S2","Solid Or Stranded":"2x (0.75 ... 16 mm²)","Product Brand Name":"SIRIUS","Degree Of Pollution":"3","Product Designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 500 V rated value":"22 kW","at 60 Hz rated value":"480 V","at 690 V rated value":"11.4 kW","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","at AC-2 at 400 V rated value":"18.5 kW","at AC-4 at 400 V rated value":"35 A","Substance Prohibitance (Date)":"01.05.2012","at 40 °C minimum permissible":"16 mm²","at 60 °C minimum permissible":"16 mm²","Insulation Voltage Rated Value":"690 V","at 230 V at 60 °C rated value":"22 kW","at 690 V at 60 °C rated value":"66 kW","at AWG cables for main contacts":"2x (18 ... 2)","For Auxiliary And Control Circuit":"spring-loaded terminals","With Type Of Assignment 2 Required":"fuse gL/gG: 63 A","reference code acc. to IEC 81346-2":"Q","Surge Voltage Resistance Rated Value":"6 kV","With Type Of Coordination 1 Required":"fuse gL/gG: 125 A","at AWG cables for auxiliary contacts":"2x (24 ... 14)","operational current at AC-12 maximum":"10 A","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.25 ... 1.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","Thermal Short-Time Current Limited To 10 S":"400 A","Finely Stranded Without Core End Processing":"2x (0.25 ... 2.5 mm²)","apparent holding power of magnet coil at AC":"12.6 V·A","apparent pick-up power of magnet coil at AC":"166 V·A","Type Of Voltage Of The Control Supply Voltage":"AC","Required Spacing For Grounded Parts At The Side":"6 mm","contact rating of auxiliary contacts according to UL":"A600 / Q600","Inductive Power Factor With Closing Power Of The Coil":"0.71","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Inductive Power Factor With The Holding Power Of The Coil":"0.37","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"0","number of NO contacts for auxiliary contacts instantaneous contact":"0","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=317219&mlfb=3RT1035-3AV60","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1035-3AV60/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional second-source to 3RT1035-3AV60?","answer":"The 3RT1026-1AB00 is a smaller S0-frame contactor from the same SIRIUS family. It will not drop into the same panel footprint without rewiring — the S2 frame is wider (55 mm vs S0's 45 mm) and has different terminal spacing. For a direct drop-in replacement within the same S2 frame, consider the 3RT5035-1AH00 or 3RT5036-1AP00, but verify coil voltage and auxiliary configuration against your BOM."},{"question":"Will 3RT1035-3AV60 drop into a panel that was specified around 3RT1026-1AB00 without rewiring?","answer":"No. The S2 frame (55 mm wide) is physically larger than the S0 frame of 3RT1026-1AB00 (45 mm wide). The DIN rail mounting is the same standard 35 mm rail, but the terminal positions and spacing differ — expect to re-terminate the main and control wires."},{"question":"What compliance documentation does this brand provide for 3RT1035-3AV60?","answer":"The part carries a substance prohibition date of 01.05.2012, confirming RoHS compliance per EU Directive 2011/65/EU. The design follows IEC 60947-4-1 for contactors. Siemens provides RoHS and REACH declarations on request."},{"question":"How do I get current pricing and availability for 3RT1035-3AV60?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1035-3AV60","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1035-3AV60 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}