{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1036-1AF00","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1036-1AF00","canonicalUrl":"https://aoctrl.com/siemens/3RT1036-1AF00","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1036-1AF00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, 3RT1036-1AF00, S2 frame, 22 kW AC-2 at 400 V, 110 V 50 Hz coil, screw terminals, current lifecycle.","salesMarkdown":"The 110 V 50 Hz coil pulls in reliably across the 0.8 to 1.1 times rated voltage range. Screw-type terminals on the main circuit accept stranded cable up to 2x 25 mm², and solid or ferrule-terminated conductors from 0.5 mm² up to 4 mm² on the auxiliary circuit. This contactor is not explicitly rated for AC-3 in the evidence, but the AC-2 rating of 22 kW at 400 V confirms it is sized for slip-ring or wound-rotor motor applications. Maximum switching frequency varies by duty: 1000 cycles/hour for AC-1 (resistive loads), 400 for AC-2, 800 for AC-3, and 300 for AC-4 — the AC-4 figure is the limiting one for high-cycle jogging applications. The S2 frame occupies 55 mm width, 112 mm height, 115 mm depth. Front face is IP20; the terminal area is IP00 — the panel builder must maintain clearance and cover live parts as part of the overall enclosure rating. ## Wire termination details Main circuit screw terminals accept stranded conductors from 2x 0.75 mm² up to 2x 25 mm². Auxiliary circuit terminals handle solid wire from 0.5 mm² to 4 mm² (max 2x 4 mm²). Substance prohibitance date of 05/01/2012 aligns with RoHS compliance. The contactor carries the SIRIUS brand from Siemens.","metaTitle":"Siemens 3RT1036-1AF00 SIRIUS Power Contactor, 22 kW AC-2 at","metaDescription":"Siemens 3RT1036-1AF00 SIRIUS power contactor, S2 frame, 22 kW AC-2 at 400 V. Current lifecycle stage. 110 V 50 Hz coil. Screw terminals. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"115 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"55 mm","at AC":"7 ... 20 ms","Height":"112 mm","Stranded":"2x (0.75 ... 25 mm²)","at 50 Hz":"0.8 ... 1.1","Arcing Time":"10 ... 15 ms","On The Front":"IP20","1 Rated Value":"50 Hz","During Storage":"-55 ... +80 °C","Of The Terminal":"IP00","at AC-1 maximum":"1 000 1/h","at AC-2 maximum":"400 1/h","at AC-3 maximum":"800 1/h","at AC-4 maximum":"300 1/h","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Size Of Contactor":"S2","Solid Or Stranded":"2x (0.75 ... 16 mm²)","Product Brand Name":"SIRIUS","Degree Of Pollution":"3","Product Designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"110 V","at 500 V rated value":"30 kW","at 690 V rated value":"11.4 kW","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","at AC-2 at 400 V rated value":"22 kW","at AC-4 at 400 V rated value":"41 A","Substance Prohibitance (Date)":"05/01/2012","at 40 °C minimum permissible":"16 mm²","at 60 °C minimum permissible":"16 mm²","Insulation Voltage Rated Value":"690 V","at 230 V at 60 °C rated value":"22 kW","at 690 V at 60 °C rated value":"66 kW","at AWG cables for main contacts":"2x (18 ... 2)","For Auxiliary And Control Circuit":"screw-type terminals","With Type Of Assignment 2 Required":"fuse gL/gG: 80 A","Surge Voltage Resistance Rated Value":"6 kV","With Type Of Coordination 1 Required":"fuse gL/gG: 160 A","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","operational current at AC-12 maximum":"10 A","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","Thermal Short-Time Current Limited To 10 S":"400 A","Finely Stranded Without Core End Processing":"2x (0.75 ... 16 mm²)","apparent holding power of magnet coil at AC":"12.5 VA","apparent pick-up power of magnet coil at AC":"145 VA","Type Of Voltage Of The Control Supply Voltage":"AC","Required Spacing For Grounded Parts At The Side":"6 mm","contact rating of auxiliary contacts according to UL":"A600 / Q600","Inductive Power Factor With Closing Power Of The Coil":"0.79","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Inductive Power Factor With The Holding Power Of The Coil":"0.36","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"0","number of NO contacts for auxiliary contacts instantaneous contact":"0","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$160.02","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=132760&mlfb=3RT1036-1AF00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1036-1AF00/alternatives.json"},"ai":{"faq":[{"question":"What is the depth of the 3RT1036-1AF00?","answer":"The depth is 115 mm."},{"question":"What wire sizes does the 3RT1036-1AF00 accept?","answer":"Solid wire: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), max 2x (0.75 to 4 mm²). Stranded wire: 2x (0.75 to 25 mm²) on the main circuit."},{"question":"What compliance documentation does Siemens provide for 3RT1036-1AF00?","answer":"The part carries a substance prohibitance date of 05/01/2012 aligning with RoHS. As a SIRIUS product, Siemens typically provides CE, UL, CSA, and IEC declarations with the contactor."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1036-1AF00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1036-1AF00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}