{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1036-1AK60","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1036-1AK60","canonicalUrl":"https://aoctrl.com/siemens/3RT1036-1AK60","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1036-1AK60","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, Size S2, screw-type terminals, 30 kW at 500 V AC-3, 22 kW at 400 V AC-2, 115 mm depth, 55 mm width, 112 mm height.","salesMarkdown":"## Siemens SIRIUS 3RT1036-1AK60 Power Contactor The Siemens SIRIUS 3RT1036-1AK60 is a Size S2 power contactor rated for motor switching at 30 kW at 500 V AC-3 and 22 kW at 400 V AC-2. The front panel carries an IP20 rating; the terminals themselves are IP00. AC-3 rating of 30 kW at 500 V is the motor-switching capacity for standard squirrel-cage motors — this is the figure that determines whether the contactor can handle the locked-rotor current during start. The AC-2 rating of 22 kW at 400 V applies to slip-ring motors or wound-rotor applications where the load current is interrupted at lower inrush. For resistive loads (AC-1), the contactor can cycle up to 1,000 operations per hour; for AC-3, 800 per hour; for AC-4 (plugging/reversing), 300 per hour. The coil operates across a 0.8 to 1.1 range of rated voltage at 50 or 60 Hz, with arcing time between 10 and 20 ms. The 55 mm wide, 112 mm tall, 115 mm deep footprint fits standard S2 cutouts. Side-by-side mounting is allowed without derating.","metaTitle":"Siemens 3RT1036-1AK60 SIRIUS Power Contactor, Size S2, 30 kW","metaDescription":"Siemens SIRIUS 3RT1036-1AK60 power contactor, Size S2, screw terminals, 30 kW at 500 V AC-3, 22 kW at 400 V AC-2. DIN rail mount. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"115 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"55 mm","at AC":"7 ... 20 ms","Height":"112 mm","Stranded":"2x (0.75 ... 25 mm²)","at 50 Hz":"0.8 ... 1.1","at 60 Hz":"0.8 ... 1.1","Arcing Time":"10 ... 15 ms","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","During Storage":"-55 ... +80 °C","Of The Terminal":"IP00","at AC-1 maximum":"1 000 1/h","at AC-2 maximum":"400 1/h","at AC-3 maximum":"800 1/h","at AC-4 maximum":"300 1/h","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Size Of Contactor":"S2","Solid Or Stranded":"2x (0.75 ... 16 mm²)","Product Brand Name":"SIRIUS","Degree Of Pollution":"3","Product Designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"110 V","at 500 V rated value":"30 kW","at 60 Hz rated value":"120 V","at 690 V rated value":"11.4 kW","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","at AC-2 at 400 V rated value":"22 kW","at AC-4 at 400 V rated value":"41 A","Substance Prohibitance (Date)":"05/01/2012","at 40 °C minimum permissible":"16 mm²","at 60 °C minimum permissible":"16 mm²","Insulation Voltage Rated Value":"690 V","at 230 V at 60 °C rated value":"22 kW","at 690 V at 60 °C rated value":"66 kW","at AWG cables for main contacts":"2x (18 ... 2)","For Auxiliary And Control Circuit":"screw-type terminals","With Type Of Assignment 2 Required":"fuse gL/gG: 80 A","Surge Voltage Resistance Rated Value":"6 kV","With Type Of Coordination 1 Required":"fuse gL/gG: 160 A","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","operational current at AC-12 maximum":"10 A","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","Thermal Short-Time Current Limited To 10 S":"400 A","Finely Stranded Without Core End Processing":"2x (0.75 ... 16 mm²)","apparent holding power of magnet coil at AC":"12.6 VA","apparent pick-up power of magnet coil at AC":"166 VA","Type Of Voltage Of The Control Supply Voltage":"AC","Required Spacing For Grounded Parts At The Side":"6 mm","contact rating of auxiliary contacts according to UL":"A600 / Q600","Inductive Power Factor With Closing Power Of The Coil":"0.71","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Inductive Power Factor With The Holding Power Of The Coil":"0.37","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"0","number of NO contacts for auxiliary contacts instantaneous contact":"0","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$515.16","priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=247824&mlfb=3RT1036-1AK60","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1036-1AK60/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for 3RT1036-1AK60?","answer":"Submit an RFQ through this listing; availability and current pricing are confirmed at quote time."},{"question":"What is 3RT1036-1AK60's depth?","answer":"The depth is 115 mm."},{"question":"What solid wire sizes does the terminal accept?","answer":"The screw terminals accept 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), and max 2x (0.75 to 4 mm²) solid conductors."},{"question":"Will 3RT1036-1AK60 drop into a panel specified for 3RT5036-1AP00 without rewiring?","answer":"No — the 3RT5036-1AP00 is a different frame size (S0 vs S2) with different dimensions and terminal layout; the 3RT1036-1AK60 will not mechanically interchange without panel modifications."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1036-1AK60","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1036-1AK60 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}