{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1036-1AK60-ZX95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1036-1AK60-ZX95","canonicalUrl":"https://aoctrl.com/siemens/3RT1036-1AK60-ZX95","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1036-1AK60-ZX95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS, power contactor, size S2, 3RT1036-1AK60-ZX95, screw-type terminals, 22 kW at AC-2 400 V, snap-on mounting on 35 mm DIN rail.","salesMarkdown":"Its headline rating is 22 kW at AC-2 duty at 400 V — that is the current it can make and break for slip-ring motor starting, where the load current stays below the inrush peak. The front face carries an IP20 rating; the terminals themselves are IP00, meaning the wiring compartment expects enclosure protection from the panel. ## Thermal and mechanical endurance Mechanical life is typical 10,000,000 operations — that is the unloaded cycle count before wear-out. Electrical life depends on duty: at AC-1 (resistive loads) it manages 1,000 cycles per hour maximum; at AC-3 (motor running) 800 cycles per hour; at AC-4 (plugging/inching) it drops to 300 cycles per hour. Pollution degree 3 means it tolerates conductive pollution in industrial atmospheres — typical for a panel-mounted contactor not in a sealed clean room. ## Termination and wiring Main current circuit uses screw-type terminals. Solid conductors accept 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), and max 2x (0.75 to 4 mm²). Stranded conductors go up to 2x (0.75 to 25 mm²) for the main circuit, with a separate solid-or-stranded range of 2x (0.75 to 16 mm²). That covers most panel wiring from control-signal cross-sections up to motor feeder cables.","metaTitle":"Siemens 3RT1036-1AK60-ZX95 SIRIUS Power Contactor, S2, 22 kW","metaDescription":"Siemens 3RT1036-1AK60-ZX95 SIRIUS power contactor, size S2, rated 22 kW at AC-2 400 V. Screw terminals, snap-on DIN rail. IP20 front. Current lifecycle stage. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"115 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"55 mm","at AC":"7 ... 20 ms","Height":"112 mm","Stranded":"2x (0.75 ... 25 mm²)","at 50 Hz":"0.8 ... 1.1","at 60 Hz":"0.8 ... 1.1","Arcing Time":"10 ... 15 ms","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","During Storage":"-55 ... +80 °C","Of The Terminal":"IP00","at AC-1 maximum":"1 000 1/h","at AC-2 maximum":"400 1/h","at AC-3 maximum":"800 1/h","at AC-4 maximum":"300 1/h","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Size Of Contactor":"S2","Solid Or Stranded":"2x (0.75 ... 16 mm²)","Product Brand Name":"SIRIUS","Degree Of Pollution":"3","Product Designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"110 V","at 500 V rated value":"30 kW","at 60 Hz rated value":"120 V","at 690 V rated value":"11.4 kW","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","at AC-2 at 400 V rated value":"22 kW","at AC-4 at 400 V rated value":"41 A","Substance Prohibitance (Date)":"05/01/2012","at 40 °C minimum permissible":"16 mm²","at 60 °C minimum permissible":"16 mm²","Insulation Voltage Rated Value":"690 V","at 230 V at 60 °C rated value":"22 kW","at 690 V at 60 °C rated value":"66 kW","at AWG cables for main contacts":"2x (18 ... 2)","For Auxiliary And Control Circuit":"screw-type terminals","With Type Of Assignment 2 Required":"fuse gL/gG: 80 A","Surge Voltage Resistance Rated Value":"6 kV","With Type Of Coordination 1 Required":"fuse gL/gG: 160 A","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","operational current at AC-12 maximum":"10 A","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","Thermal Short-Time Current Limited To 10 S":"400 A","Finely Stranded Without Core End Processing":"2x (0.75 ... 16 mm²)","apparent holding power of magnet coil at AC":"12.6 VA","apparent pick-up power of magnet coil at AC":"166 VA","Type Of Voltage Of The Control Supply Voltage":"AC","Required Spacing For Grounded Parts At The Side":"6 mm","contact rating of auxiliary contacts according to UL":"A600 / Q600","Inductive Power Factor With Closing Power Of The Coil":"0.71","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Inductive Power Factor With The Holding Power Of The Coil":"0.37","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"0","number of NO contacts for auxiliary contacts instantaneous contact":"0","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=2192&mlfb=3RT1036-1AK60-ZX95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1036-1AK60-ZX95/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3RT1036-1AK60-ZX95 and get a price?","answer":"This part is sourced and quoted to order through independent distribution. Submit an RFQ for current availability and pricing — no stock count or price is published here."},{"question":"What is the closest functional second-source to 3RT1036-1AK60-ZX95?","answer":"The 3RT5036-1AP00 is a SIRIUS contactor in the same S2 frame, but it is a different variant with its own coil and auxiliary configuration. It will not drop into a panel wired for this order code without verifying the coil voltage and terminal layout — check the specific datasheet before substituting."},{"question":"What is the depth of 3RT1036-1AK60-ZX95?","answer":"The depth is 115 mm, with a width of 55 mm and height of 112 mm."},{"question":"What solid conductor sizes does this contactor accept?","answer":"Solid conductors: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), and max 2x (0.75 to 4 mm²). Stranded: 2x (0.75 to 25 mm²) for the main circuit."},{"question":"What compliance documentation is available for this contactor?","answer":"The product is a Siemens SIRIUS power contactor. Standard compliance documentation (CE, RoHS, REACH) is provided by the manufacturer. Specific certificates should be requested at time of order."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1036-1AK60-ZX95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1036-1AK60-ZX95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}