{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1036-1AL00","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1036-1AL00","canonicalUrl":"https://aoctrl.com/siemens/3RT1036-1AL00","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1036-1AL00","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S2, 3RT1036-1AL00, screw-type terminals, 22 kW at AC-2 400 V, 41 A AC-4, 55 mm width, DIN EN 50022 rail mount.","salesMarkdown":"## Siemens 3RT1036-1AL00 SIRIUS Power Contactor — Field Integration Note It carries a 22 kW rating at AC-2 duty at 400 V and a 41 A rating at AC-4 duty at 400 V — the AC-2 figure governs standard slip-ring motor starting, while the AC-4 rating covers reversing and inching applications where the contactor makes and breaks stalled rotor current. ## Switching Frequency and Thermal Limits Maximum switching rates are duty-dependent: 1 000 cycles per hour at AC-1 (resistive), 800 at AC-3 (normal motor start), 400 at AC-2, and 300 at AC-4. Main current circuit connections use screw-type terminals. Solid conductors accepted: 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), max 2x (0.75 to 4 mm²). Stranded conductors: 2x (0.75 to 25 mm²) for the main circuit, and solid or stranded 2x (0.75 to 16 mm²) for auxiliary circuits. The 55 mm width and 112 mm height fit the standard S2 footprint; depth is 115 mm including the arc chamber. Coil operating range at 50 Hz is 0.8 to 1.1 times rated voltage, with pick-up time of 7 to 20 ms at AC.","metaTitle":"Siemens 3RT1036-1AL00 SIRIUS Power Contactor, 22 kW AC-2, 41","metaDescription":"Siemens 3RT1036-1AL00 SIRIUS power contactor, size S2, 22 kW at AC-2 400 V, 41 A AC-4. Screw terminals, DIN rail mount, IP20 front. Active production, sourced to order. Request quo","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"115 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"55 mm","at AC":"7 ... 20 ms","Height":"112 mm","Stranded":"2x (0.75 ... 25 mm²)","at 50 Hz":"0.8 ... 1.1","Arcing Time":"10 ... 15 ms","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","During Storage":"-55 ... +80 °C","Of The Terminal":"IP00","at AC-1 maximum":"1 000 1/h","at AC-2 maximum":"400 1/h","at AC-3 maximum":"800 1/h","at AC-4 maximum":"300 1/h","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Size Of Contactor":"S2","Solid Or Stranded":"2x (0.75 ... 16 mm²)","Product Brand Name":"SIRIUS","Degree Of Pollution":"3","Product Designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"125 V","at 500 V rated value":"30 kW","at 690 V rated value":"11.4 kW","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","at AC-2 at 400 V rated value":"22 kW","at AC-4 at 400 V rated value":"41 A","Substance Prohibitance (Date)":"05/01/2012","at 40 °C minimum permissible":"16 mm²","at 60 °C minimum permissible":"16 mm²","Insulation Voltage Rated Value":"690 V","at 230 V at 60 °C rated value":"22 kW","at 690 V at 60 °C rated value":"66 kW","at AWG cables for main contacts":"2x (18 ... 2)","For Auxiliary And Control Circuit":"screw-type terminals","With Type Of Assignment 2 Required":"fuse gL/gG: 80 A","Surge Voltage Resistance Rated Value":"6 kV","With Type Of Coordination 1 Required":"fuse gL/gG: 160 A","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","operational current at AC-12 maximum":"10 A","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","Thermal Short-Time Current Limited To 10 S":"400 A","Finely Stranded Without Core End Processing":"2x (0.75 ... 16 mm²)","apparent holding power of magnet coil at AC":"12.5 VA","apparent pick-up power of magnet coil at AC":"145 VA","Type Of Voltage Of The Control Supply Voltage":"AC","Required Spacing For Grounded Parts At The Side":"6 mm","contact rating of auxiliary contacts according to UL":"A600 / Q600","Inductive Power Factor With Closing Power Of The Coil":"0.79","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Inductive Power Factor With The Holding Power Of The Coil":"0.36","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"0","number of NO contacts for auxiliary contacts instantaneous contact":"0","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=109689&mlfb=3RT1036-1AL00","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1036-1AL00/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings for the 3RT1036-1AL00?","answer":"The contactor is rated 22 kW at AC-2 duty at 400 V and 41 A at AC-4 duty at 400 V. Maximum switching frequency is 1 000 ops/h at AC-1, 800 at AC-3, 400 at AC-2, and 300 at AC-4."},{"question":"Where can I buy the 3RT1036-1AL00 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at the time of quote — submit an RFQ for a firm price and lead time."},{"question":"What is the closest functional alternative to the 3RT1036-1AL00?","answer":"The 3RT5036-1AP00 is a peer in the same S2 frame size with similar AC-3 motor ratings, but it uses spring-cage terminals instead of screw-type. Panel rewiring would be required if switching from screw to spring-cage termination."},{"question":"Does the 3RT1036-1AL00 comply with RoHS?","answer":"Yes, the part carries a RoHS substance prohibition date of 05/01/2012, confirming compliance with EU RoHS requirements for the listed substances."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1036-1AL00","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1036-1AL00 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}