{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1036-1AN24-ZX95","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1036-1AN24-ZX95","canonicalUrl":"https://aoctrl.com/siemens/3RT1036-1AN24-ZX95","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1036-1AN24-ZX95","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S2, 3RT1036-1AN24-ZX95, screw-type terminals, 55 mm width, 30 kW at 500 V AC-3.","salesMarkdown":"The contactor is rated for 30 kW at 500 V and 11.4 kW at 690 V in AC-3 duty, which covers most three-phase induction motor applications in that power band. For AC-2 duty (slip-ring motors or reversing starts), it carries 22 kW at 400 V. The coil is wound for 220 V at both 50 Hz and 60 Hz, with an operating range of 0.8...1.1 times rated voltage at 50 Hz and 0.85...1.1 at 60 Hz. That means the coil holds in reliably even if the line voltage sags to about 176 V on a 50 Hz supply. The contactor body measures 55 mm wide by 112 mm high by 164 mm deep. At 55 mm, it occupies a standard three-module width on the DIN rail, so you can plan your enclosure fill factor accordingly. Side-by-side mounting is permitted, which means no mandatory spacing between contactors on the rail. The main power circuit uses screw-type terminals, accepting solid conductors from 2x 0.5...1.5 mm² up to max 2x 0.75...4 mm², and stranded conductors from 2x 0.75...25 mm². That range covers standard motor cables up to about 6 AWG stranded, so no lugging or adapter needed for most installations. Auxiliary contact ratings are given at multiple voltages: 10 A at 24 V, 6 A at 230 V, and 3 A at 400 V. These are the make/break capacities for the control circuit, so verify your PLC output or relay load stays within these limits per the voltage you're switching. That's standard for panel-mounted contactors — the enclosure provides the overall IP rating, and the contactor's own terminal protection is minimal because it's inside a cabinet. That covers most factory-floor panels without special derating. No last-time-buy urgency or broker-channel scavenging needed for this order code.","metaTitle":"Siemens 3RT1036-1AN24-ZX95 SIRIUS Power Contactor, S2, 55 mm","metaDescription":"Siemens 3RT1036-1AN24-ZX95 SIRIUS power contactor, size S2, 55 mm width, screw terminals, 30 kW at 500 V. Current lifecycle stage. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"164 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"55 mm","at AC":"7 ... 20 ms","Height":"112 mm","Stranded":"2x (0.75 ... 25 mm²)","at 50 Hz":"0.8 ... 1.1","at 60 Hz":"0.85 ... 1.1","Arcing Time":"10 ... 15 ms","On The Front":"IP20","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","During Storage":"-55 ... +80 °C","Of The Terminal":"IP00","at AC-1 maximum":"1 000 1/h","at AC-2 maximum":"400 1/h","at AC-3 maximum":"800 1/h","at AC-4 maximum":"300 1/h","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Fastening Method":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","Size Of Contactor":"S2","Solid Or Stranded":"2x (0.75 ... 16 mm²)","Product Brand Name":"SIRIUS","Degree Of Pollution":"3","Product Designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"220 V","at 500 V rated value":"30 kW","at 60 Hz rated value":"220 V","at 690 V rated value":"11.4 kW","Side-By-Side Mounting":"Yes","For Main Current Circuit":"screw-type terminals","at AC-2 at 400 V rated value":"22 kW","at AC-4 at 400 V rated value":"41 A","Substance Prohibitance (Date)":"05/01/2012","at 40 °C minimum permissible":"16 mm²","at 60 °C minimum permissible":"16 mm²","Insulation Voltage Rated Value":"690 V","at 230 V at 60 °C rated value":"22 kW","at 690 V at 60 °C rated value":"66 kW","at AWG cables for main contacts":"2x (18 ... 2)","For Auxiliary And Control Circuit":"screw-type terminals","With Type Of Assignment 2 Required":"fuse gL/gG: 80 A","Surge Voltage Resistance Rated Value":"6 kV","With Type Of Coordination 1 Required":"fuse gL/gG: 160 A","at AWG cables for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","operational current at AC-12 maximum":"10 A","number of NC contacts for main contacts":"0","number of NO contacts for main contacts":"3","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number Of Poles For Main Current Circuit":"3","Contact Reliability Of Auxiliary Contacts":"1 faulty switching per 100 million (17 V, 1 mA)","Thermal Short-Time Current Limited To 10 S":"400 A","Finely Stranded Without Core End Processing":"2x (0.75 ... 16 mm²)","apparent holding power of magnet coil at AC":"15 VA","apparent pick-up power of magnet coil at AC":"170 VA","Type Of Voltage Of The Control Supply Voltage":"AC","Required Spacing For Grounded Parts At The Side":"6 mm","contact rating of auxiliary contacts according to UL":"A600 / Q600","Inductive Power Factor With Closing Power Of The Coil":"0.76","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","Inductive Power Factor With The Holding Power Of The Coil":"0.35","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","number of NC contacts for auxiliary contacts instantaneous contact":"2","number of NO contacts for auxiliary contacts instantaneous contact":"2","Of The Contactor With Added Electronically Optimized Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=379300&mlfb=3RT1036-1AN24-ZX95","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1036-1AN24-ZX95/alternatives.json"},"ai":{"faq":[{"question":"What are the key dimensions for panel layout?","answer":"The contactor is 55 mm wide, 112 mm high, and 164 mm deep. It mounts on 35 mm DIN rail and allows side-by-side mounting without spacing."},{"question":"What conductor sizes does the screw terminal accept?","answer":"Solid conductors: 2x 0.5...1.5 mm², 2x 0.75...2.5 mm², max 2x 0.75...4 mm². Stranded conductors: 2x 0.75...25 mm². That covers most motor cables up to about 6 AWG stranded."},{"question":"What motor power can this contactor switch?","answer":"In AC-3 duty, it is rated for 30 kW at 500 V and 11.4 kW at 690 V. For AC-2 duty, it carries 22 kW at 400 V."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1036-1AN24-ZX95","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1036-1AN24-ZX95 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}