{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RT1036-1AP00-ZW98","brand":"Siemens","brandSlug":"siemens","productSlug":"3RT1036-1AP00-ZW98","canonicalUrl":"https://aoctrl.com/siemens/3RT1036-1AP00-ZW98","factsUrl":"https://aoctrl.com/api/mcp/products/3RT1036-1AP00-ZW98","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS power contactor, size S2, 3RT1036-1AP00-ZW98, rated insulation voltage 690 V, screw-type terminals, snap-on mounting.","salesMarkdown":"The 690 V rated insulation voltage covers most 400 V and 480 V line-to-line systems with headroom for grounded-wye configurations. The S2 frame size determines the physical footprint and the maximum contactor current — expect this to handle motor currents typical of a 30 kW load at 500 V or 11.4 kW at 690 V. Screw-type terminals on the main circuit accept solid conductors from 2x 0.5 mm² up to 2x 4 mm² and stranded up to 2x 25 mm². That's enough for most motor feeder cables up to 6 AWG. The IP20 front means it's finger-safe once installed in a closed panel; the terminal area itself is IP00, so live parts are exposed during wiring — standard for panel-mount contactors. Mechanical life is typical at 10 million operations. Switching frequency ranges from 300 cycles/hour at AC-4 (the toughest motor inching/jogging duty) up to 1,000 cycles/hour at AC-1 (resistive loads). For a motor-starting application (AC-3), expect 800 cycles/hour.","metaTitle":"Siemens 3RT1036-1AP00-ZW98 SIRIUS Power Contactor, S2, 690 V","metaDescription":"Siemens SIRIUS power contactor 3RT1036-1AP00-ZW98, size S2, rated 690 V. Current production. Screw terminals, snap-on DIN rail. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Contactors"],"specifications":{"Depth":"115 mm","Solid":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)","Width":"55 mm","at AC":"7 ... 20 ms","Height":"112 mm","Maximum":"2 000 m","Stranded":"2x (0.75 ... 25 mm²)","at 50 Hz":"0.8 ... 1.1","Arcing time":"10 ... 15 ms","At The Side":"6 mm","Rated Value":"690 V","On The Front":"IP20","1 Rated Value":"50 Hz","Mounting type":"screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022","During Storage":"-55 ... +80 °C","Of The Terminal":"IP00","at AC-1 maximum":"1 000 1/h","at AC-2 maximum":"400 1/h","at AC-3 maximum":"800 1/h","at AC-4 maximum":"300 1/h","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","Size of contactor":"S2","Product brand name":"SIRIUS","Degree of pollution":"3","Product designation":"power contactor","at 24 V rated value":"10 A","at 60 V rated value":"2 A","Of Contactor Typical":"10 000 000","at 110 V rated value":"1 A","at 220 V rated value":"0.3 A","at 230 V rated value":"6 A","at 400 V rated value":"3 A","at 50 Hz rated value":"230 V","at 500 V rated value":"30 kW","at 690 V rated value":"11.4 kW","Instantaneous Contact":"0","Side-by-side mounting":"Yes","For Main Current Circuit":"screw-type terminals","Single Or Multi-Stranded":"2x (0,75 ... 16 mm²)","at AC-2 at 400 V rated value":"22 kW","at AC-4 at 400 V rated value":"41 A","at 40 °C minimum permissible":"16 mm²","at 60 °C minimum permissible":"16 mm²","at 230 V at 60 °C rated value":"22 kW","at 690 V at 60 °C rated value":"66 kW","Operating current at AC-12 maximum":"10 A","With Type Of Assignment 2 Required":"fuse gL/gG: 80 A","at AWG conductors for main contacts":"2x (18 ... 2)","Surge voltage resistance rated value":"6 kV","With Type Of Coordination 1 Required":"fuse gL/gG: 160 A","Reference code acc. to DIN EN 81346-2":"Q","Number of NC contacts for main contacts":"0","Number of NO contacts for main contacts":"3","Finely Stranded With Core End Processing":"2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)","Number of poles for main current circuit":"3","at AWG conductors for auxiliary contacts":"2x (20 ... 16), 2x (18 ... 14), 1x 12","Contact reliability of auxiliary contacts":"1 faulty switching per 100 million (17 V, 1 mA)","For Auxiliary And Control Current Circuit":"screw-type terminals","at ambient temperature 40 °C rated value":"60 A","Thermal short-time current limited to 10 s":"400 A","Apparent holding power of magnet coil at AC":"12.5 V·A","Apparent pick-up power of magnet coil at AC":"145 V·A","Finely Stranded Without Core End Processing":"2x (0.75 ... 16 mm²)","Type of voltage of the control supply voltage":"AC","between coil and main contacts acc. to EN 60947-1":"400 V","Contact rating of auxiliary contacts according to UL":"A600 / Q600","Inductive power factor with closing power of the coil":"0.79","Inductive power factor with the holding power of the coil":"0.36","Of The Contactor With Added Auxiliary Switch Block Typical":"10 000 000","For Short-Circuit Protection Of The Auxiliary Switch Required":"fuse gL/gG: 10 A","Of The Contactor With Added Electronics-Compatible Auxiliary Switch Block Typical":"5 000 000"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=309184&mlfb=3RT1036-1AP00-ZW98","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RT1036-1AP00-ZW98/alternatives.json"},"ai":{"faq":[{"question":"What is the closest functional second-source?","answer":"The Siemens 3RT1036-1AB00 is a direct sibling in the same S2 frame size. The key difference is the coil voltage — the -1AP00 variant uses a different coil rating than the -1AB00. Verify coil voltage compatibility before substituting."},{"question":"What is the depth of this contactor?","answer":"The depth is 115 mm. Combined with a width of 55 mm and height of 112 mm, it fits a standard 55 mm wide DIN-rail slot."},{"question":"What wire sizes does the screw terminal accept?","answer":"Solid conductors: 2x 0.5 to 1.5 mm², 2x 0.75 to 2.5 mm², max 2x 0.75 to 4 mm². Stranded: 2x 0.75 to 25 mm²."},{"question":"Will this drop into a panel designed for 3RT1036-1AB00?","answer":"Yes, same S2 frame size and mounting footprint. The physical dimensions and terminal layout are identical. The only difference is the coil — check that the coil voltage matches your control circuit."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RT1036-1AP00-ZW98","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RT1036-1AP00-ZW98 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}